REFRIGERANT PIPE CONNECTION
Settlement of outdoor unit
Anchor the outdoor unit with a bolt and
nut
10 or
8 tightly and horizontally
on a concrete or rigid mount.
A
B
Air inlet
Air outlet
Air inlet
Fig.14
Refrigerant pipe connection
Oblique
90
Roughness
Burr
Main cause for refrigerant leakage
is due to defect in the flaring work.
Carry out correct flaring work
using the following procedure:
A: Cut the pipes and the cable.
1. Use the piping kit accessory or pipes
purchased locally.
2. Measure the distance between the indoor
and the outdoor unit.
3. Cut the pipes a little longer than the
measured distance.
4. Cut the cable 1.5m longer than the pipe
length.
1. Flaring work
Fig.15
B: Burr removal
1. Completely remove all burrs from the cut
cross section of pipe/tube.
2. Put the end of the copper tube/pipe in a
downward direction as you remove burrs in
order to avoid dropping burrs into the tubing.
Pipe
Reamer
Point down
Fig.16
Fig.17
Outdoor unit dimension
mm(WxHxD)
A(mm)
B(mm)
530
290
484
600
560
590
275
320
335
333
549
280
Mounting dimensions
780x540x250
760x590x275
670x540x250
775x545x310
840x700x320
895x860x330
Drain joint installation
Seal
Drain joint
Base pan hole of
outdoor unit
Seal
Drain pipe
(A)
(B)
For the drain joint with the seal(Fig.15 (A)), first
fit the seal onto the drain joint, then insert the
drain joint into the base pan hole of outdoor unit,
rotate 90
to securely assemble them. To install
drain joint as shown in Fig.15 (B), insert the drain
joint into the base pan hole of outdoor unit until it
remains fixed with a clicking sound. Connecting
the drain joint with an extension drain hose (Locally
purchased), in case of the water draining off the
outdoor unit during the heating mode.
NOTE:
The drain joint is slightly different
according to the different outdoor unit.