background image

E-mail: [email protected]

Made in Rome, New York, USA

20

TROUBlESHOOTING pROCEdURE

 

Continued

is also equipped with a one time fuse link. Should electric 

heat temperatures rise above the auto resetting limit switch, 

a non-resetting, one time fuse link will open and the heater 

will remain off.

The following current values apply when the unit is connected 

to a 230V power supply. These values include fan motor 

current. If the supply power is different, this will in turn affect 

the amp draw of the heater.

5kw = 22.3 amps,    4kw = 18 amps,     3kw = 13.5 amps.

Units With Condensate pumps

EMI Air handlers are available with an optional condensate 

pump. Condensate pumps are recommended when it is not 

possible to gravity drain the condensate from the indoor unit. 

Depending on the pump manufacture the maximum lift for 

the pump will vary. Consult the pump instructions for the 

maximum lift for the particular pump being used.

Condensate generated by the air handler will collect in the 

pumps’ reservoir. When the water level is high enough, a 

float switch will close and energize the pump motor clearing 

the water from the reservoir. Should for any reason the 

water exceed the maximum preset level, a safety switch 

will  open,  there  by  interrupting  the  (Y)  signal. This  will 

prevent the air handler from generating more condensate 

and spilling out of the unit.

Error Codes

Should for some reason one of the two temperature 

sensors become disconnected or fail, an error code 

will appear in the display. The control will not operate 

properly until the sensor is working.

E1

  –  Coil  Sensor  malfunction  or  disconnected.  Check 

location 

J1

 on thermostat board.

E2

 – Room Air Sensor malfunction or disconnected. Check 

location 

J2

 on thermostat board.

q:

 The display on the indoor unit is blank. What should I do?

A:

  Check  the  power  supply  (see  “Power  supply  check” 

Section). If the unit still fails to turn on via the 

On/off

 

button then inspect the control box for any apparent wires 

that may have come loose during shipping. Also inspect 

the circuit boards for burnt components. If no obvious 

problem  can  be  found  then  replace  all  circuit  boards 

including the unit keypad. Do not attempt to trouble shoot 

the individual circuit boards.

q:

 The display tends to flicker at times. Is this normal?

A:

 A  small amount  of  flickering of  the  display is  normal. 

Depending on the room lighting, flickering may be more 

noticeable at some times than others.

q:

 how long will the fan run?

A:

  While  the  unit  is  in  cooling  or  heating  and  auto  fan 

mode is selected, Fan speed will be determined by the 

microprocessor  and  speed  adjustment  will  be  made 

according  to  room  and  setpoint  temperatures.  The 

fan will switch to 

high

 speed when room temperature 

deviates by more than two degrees from setpoint. The 

fan  will  switch  to 

Low 

speed  if  the  deviation  is  one 

degree. When the room temperature reaches setpoint 

temperature the heat/cool call is dropped. The fan will 

then stay on for an additional 60 sec. to purge unit of any 

residual energy. If 

high

 or 

Low

 is selected then the fan 

will operate continuous regardless of set point or room 

temperatures.

q:

 What causes my indoor unit to freeze-up?

A:

 Evaporator freeze up is usually the symptom of another 

problem. Units with infrared compatible, unit mounted 

controls are equipped with freeze protection to prevent 

freeze up from occurring. If freeze up does occur then 

check the following.

  Check that the freeze sensor located in the lowest 

part of the coil. Generally this is where freeze up 

will begin.

•  Check that the freeze sensor inserted fully and snug 

in the coil fin. If not another location may need to be 

selected. Be careful not to insert the sensor directly 

into the coil tube rather insert the sensor between two 

tubes.

•  Check the indoor air filter. It should be clean and free 

of dirt. A dirty filter will reduce airflow and efficiency. 

Also check that the coil is clean. If the coil is dirty then 

it should be cleaned using an appropriate coil cleaner 

or mild detergent.

Содержание ComfortWave CCP Series

Страница 1: ...ration and maintenance MANUAL EMI DUCTLESS CHILL WATER AIR HANDLERS WALL MOUNTED AIR HANDLER WCP CEILING MOUNTED AIR HANDLER CcP An ISO 9001 2000 Certified Company Enviromaster International LLC 5780...

Страница 2: ...resulting in fire electrical shock property damage personal injury or death TO THE INSTALLER 1 Retain this manual and warranty for future refer ence 2 Before leaving the premises review this manual t...

Страница 3: ...ping Hot water piping The EMIair handler is available as a wall or ceiling unit two pipe chilled water fan coil model The air handler offers ease of installation operation and service Presently EMI do...

Страница 4: ...red when locating the unit The cabinet service panels must be able to be removed without obstruction CCP units can be equipped with hot water coil Unit mount control panel standard on and WCP optional...

Страница 5: ...nnect wiring for Unit mounted controls Remote Thermostat Controls A 24V control transformer is located in the air handler unit This provides low volt control power to the air handler Depending on the...

Страница 6: ...Figure 3 according to the table below Figure 4 CCP to gain access to the relay board first remove the return air grill from the bottom of the unit The relay board is located in the control section Se...

Страница 7: ...els Optional trim kits are available for surface mounting applications NOTE If equipped with hydronic heat the CCP will only operate as a single stage heating unit and not as a two stage heating unit...

Страница 8: ...6 42 48 64 2 CCP DISCHARGE AIR SPEED AND THROW Model CFM Coil FPM Throw Ft 09 12 350 Dry 290 12 4 18 650 Dry 430 18 6 24 30 800 Dry 533 18 6 36 42 48 1200 Dry 500 19 0 CCP HYDRONIC HEAT SPECIFICATIONS...

Страница 9: ...of this manual for more detailes on controls components electrical wiring start up Opera tion and Cleaning Maintenance MOUNTING preparation The WCP must be mounted plumb and level to a vertically squa...

Страница 10: ...t programs design and specifications may change without notice WCP WCP PHYSICAL DIMENSIONS Model Width A Height B Depth C Width D Width E Width F Width G Width H Width I Shipping Wt 09 12 36 14 10 22...

Страница 11: ...30 5 21 7 22 3 27 9 30 WCP CAPACITIES Model Nominal Capacaties Total Capacity Sensible Capacity Fluid Temp Fluid Flow PD Ft H2 0 09 12 9 000 7 375 6 732 45 1 0 8 10 801 8 272 45 2 3 8 13 270 9 279 45...

Страница 12: ...is designed to protect the system Operation of the unit can be made by either the keypad on the unit or by using the optional hand held infrared controller There are two dipswitches on the relay board...

Страница 13: ...ode button selection will rotate between Heat Cool Fan or Dry mode If the dipswitches are set for cooling only off off then Heat and Dry will not be accessible figure 5 Cooling only operation For cool...

Страница 14: ...stepoint temperature The fan will operate continuously at low speed while in Dry Mode Optional Electric heat operation Important The dip switch 1 2 must be set to ON For electric heat operation first...

Страница 15: ...ble with a cooling electric heat system The thermostat should have R Y W and G terminals The thermostat may also have a C terminal Start up for wall Thermostat Control INFRARED Remote Control Option O...

Страница 16: ...e selected in lieu of electric heat Heating operation is essentially the same as that of units with electric heat With the thermostat system switch set to heat and the set point temperature above room...

Страница 17: ...el Number Technician Serial Number Mode Cooling Indoor Section Notes Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving Air WB Outdoor Section Entering...

Страница 18: ...All service should be performed by a qualified service technician Before removing access panels or control covers to expose moving parts of non insulated live electrical components for service disconn...

Страница 19: ...tat connection A 24V transformer located in the indoor air handler unit provides low volt control power to the indoor air handler The 24v power supply can be measured by placing a meter across the R a...

Страница 20: ...f button then inspect the control box for any apparent wires that may have come loose during shipping Also inspect the circuit boards for burnt components If no obvious problem can be found then repla...

Отзывы: