CACG/CAHG & CACH/CAHH
Air Handlers
• Installation, Operation and Maintenance Manual •
Comfort where it counts
60
P/N 240008108, Rev. B [082509]
Specifications
CACG/CAHG/CACH/CAHH electrical specifications
Table 10
Model
Fan Motor
Elect Heat
Total
AMPS
Min
Volt
M.C.A.
HACR
BRKR
Volts/HZ/PH
RLA
H.P.
kW
AMPS
CAHG/H 9/12
208/230/60/1 0 35
1/10
–
–
0 4
197
0 5
15
CAHG/H 9/12
208/230/60/1 0 35
1/10
1 5
6 52
6 9
197
8 6
15
CAHG/H 24
208/230/60/1 0 55
1/8
–
–
0 6
197
0 7
15
CAHG/H 24
208/230/60/1 0 55
1/8
3
13 04
13 6
197
17 0
20
CACG/H 36
208/230/60/1 0 5, 0 5 1/10, 1/10
–
–
1 0
197
1 2
15
CACG/H 36
208/230/60/1 0 5, 0 5 1/10, 1/10
5
21 74
22 7
197
28 3
30
Technical data
Table 11
Refrigerant Type
R410A
CONNECTIONS
Model
9 &12
24
36
Suction
½”
¾” *
¾”
Liquid
¼”
3/8”
3/8”
Condensate Drain
½” I D
½” I D
½” I D
Branch Duct
5¼” Ø
5¼” Ø
5¼” Ø
Fresh Air Duct
1¼ x
2½”
3” x 3”
3” x 3”
FILTRATION
Model
9 & 12
24
36
Type
Washable Mesh
Quantity
1
2
3
Efficiency
80%
CONDENSATE
PUMP
Model
9 & 12
24
36
Maximum Head
36” (0 9 m) **
Min Flow Rate
2 5 GPH (9 5 l/h)
*Must bush down to 5/8” interconnect for 18K system
** Measured from bottom of unit
Discharge air volume (dry coil)
Table 12
Model
High Speed
CFM (L/S)
Low Speed
CFM (L/S)
9 & 12
380 (180)
335 (158)
24
700 (330)
620 (293)
36
1,300 (614)
1,160 (548)
Shipping weights
Figure 45
Model
Shipping weight — lbs (kg)
9 & 12
70 (31 8 kg)
24
108 (49 1 kg)
36
146 (66 4 kg)
Indoor sound levels (dBa)
Figure 46
Model
High Speed
Low Speed
9 & 12
41
39
24
44
42
36
51
49
NOTICE
Due to EMI’s ongoing product develop-
ment program, all designs and specifi-
cations are subject to change without