29
ZXD Family: Digital Medium Temperature
Capacity and Power (kW) at
50 Hz
- TFD
Model
Ambient
Temperature
(
o
C)
Capacity
Evaporating Temperature (
o
C)
Power
Evaporating Temperature (
o
C)
-20
-15
-10
-5
0
5
-20
-15
-10
-5
0
5
ZXD040E
27
5.92
7.11
8.35
9.64
11.01
12.46
2.70
2.85
3.02
3.21
3.43
3.68
32
5.53
6.69
7.87
9.11
10.40
11.75
2.99
3.12
3.27
3.44
3.64
3.87
38
4.90
6.00
7.12
8.27
9.45
10.68
3.49
3.59
3.72
3.87
4.04
4.24
43
4.23
5.28
6.33
7.40
8.48
9.59
4.02
4.10
4.21
4.34
4.50
4.68
48
3.56
4.56
5.54
6.53
7.51
4.55
4.61
4.70
4.81
4.96
ZXD050E
27
7.49
9.05
10.67
12.31
13.93
15.51
3.65
3.73
3.86
4.02
4.25
4.53
32
6.56
8.12
9.76
11.43
13.10
14.74
4.11
4.20
4.32
4.50
4.72
5.00
38
5.56
7.07
8.67
10.32
11.98
13.63
4.59
4.68
4.79
4.96
5.16
5.42
43
4.88
6.28
7.79
9.37
10.98
12.58
5.11
5.17
5.27
5.40
5.59
5.81
48
4.20
5.49
6.91
8.42
9.98
5.63
5.67
5.75
5.85
6.01
ZXD060E
27
8.24
9.72
11.47
13.30
15.69
18.48
3.69
3.84
4.06
4.33
4.62
4.93
32
7.58
9.06
10.72
12.58
14.72
17.20
4.40
4.54
4.75
5.01
5.28
5.56
38
6.74
8.25
9.83
11.55
13.48
15.69
4.93
5.05
5.25
5.47
5.72
5.98
43
5.90
7.48
9.07
10.74
12.57
14.63
5.59
5.69
5.85
6.06
6.28
6.51
48
5.06
6.71
8.31
9.93
11.66
6.26
6.32
6.46
6.64
6.83
ZXD075E
27
9.04
10.86
12.75
15.07
17.76
20.13
4.08
4.26
4.50
4.80
5.13
5.46
32
8.33
10.01
11.82
13.86
16.20
18.92
4.88
5.03
5.27
5.54
5.86
6.17
38
7.30
8.74
10.62
12.47
14.54
16.92
5.46
5.61
5.82
6.06
6.35
6.63
43
6.26
7.93
9.61
11.38
13.32
15.50
6.20
6.32
6.49
6.71
6.96
7.22
ZXD076E
27
9.22
11.07
13.00
15.37
18.12
20.53
4.00
4.17
4.41
4.70
5.03
5.35
32
8.50
10.21
12.06
14.14
16.53
19.30
4.78
4.93
5.16
5.43
5.74
6.05
38
7.45
8.91
10.83
12.72
14.83
17.26
5.35
5.50
5.70
5.94
6.22
6.50
43
6.39
8.09
9.80
11.61
13.59
15.81
6.07
6.19
6.36
6.57
6.82
7.07
48
5.32
7.26
8.77
10.50
12.34
6.79
6.88
7.02
7.21
7.43
Notes:
Based on return gas temperature of 18.3
o
C.
at suction superheat of 10 K.
Power include condenser fan.
Ambient 38
o
C and 43
o
C are typical design conditions for unit selection.
Capacity and Power (kW) at
60 Hz
- TF7
Model
Ambient
Temperature
(
o
C)
Capacity
Evaporating Temperature (
o
C)
Power
Evaporating Temperature (
o
C)
-20
-15
-10
-5
0
5
-20
-15
-10
-5
0
5
ZXD040E
27
7.10
8.53
9.35
10.80
12.99
14.70
3.24
3.42
3.62
3.85
4.05
4.34
32
6.64
8.03
8.70
10.20
12.27
13.87
3.59
3.74
4.00
4.13
4.30
4.57
38
5.88
7.20
7.97
9.26
11.15
12.60
4.19
4.31
4.46
4.64
4.77
5.00
43
5.21
6.34
7.09
8.29
10.01
11.32
4.82
4.92
5.05
5.21
5.31
5.52
48
4.27
5.60
6.20
7.31
8.86
5.46
5.53
5.64
5.77
5.85
ZXD050E
27
8.99
10.86
11.74
13.54
15.32
17.06
4.38
4.48
4.63
4.83
5.10
5.44
32
7.87
9.75
10.77
12.57
14.41
16.21
4.93
5.04
5.11
5.40
5.66
6.00
38
6.67
8.48
9.54
11.35
13.18
14.99
5.51
5.61
5.75
5.95
6.20
6.51
43
5.86
7.54
8.57
10.31
12.08
13.84
6.14
6.21
6.32
6.48
6.71
6.97
48
5.04
6.59
7.60
9.26
10.98
6.76
6.81
6.89
7.02
7.22
ZXD060E
27
10.22
12.06
13.41
15.56
17.89
21.07
4.42
4.61
5.08
5.41
5.78
6.16
32
9.34
11.23
12.54
14.72
16.78
19.61
5.28
5.45
5.93
6.26
6.61
6.96
38
8.36
10.23
11.50
13.51
15.37
17.89
5.91
6.06
6.58
6.83
7.15
7.47
43
7.44
9.27
10.61
12.57
14.33
16.68
6.71
6.83
7.32
7.57
7.85
8.34
48
6.27
8.22
9.72
11.62
13.29
7.51
7.59
8.07
8.30
8.54
ZXD075E
27
11.16
13.39
14.92
17.64
19.93
22.58
4.80
5.00
5.69
6.06
6.54
6.96
32
10.29
12.35
13.84
16.23
18.18
21.23
5.74
5.92
6.66
7.00
7.46
7.87
38
9.01
10.78
12.43
14.60
16.31
18.99
6.42
6.60
7.35
7.66
8.09
8.45
43
7.73
9.79
11.25
13.33
14.95
17.39
7.28
7.43
8.20
8.48
8.87
9.19
48
6.44
8.78
10.07
12.05
8.15
8.26
9.06
9.30
Notes:
Based on return gas temperature of 18.3
o
C.
at suction superheat of 10 K.
Power include condenser fan.
Ambient 38
o
C and 43
o
C are typical design conditions for unit selection.
R404A/R507 - 50 Hz
R404A/R507 - 60 Hz