Check Running Hours of Each Compressor and Reset Operation Time After Compressor Replacement
Press and release
SEtC value
Flashing
Press to select compressor number
Press and hold SET key
SEtC value
Flashing
SEtC value
Flashing
Press or wait for 30 sec
Reset Parameters by Using ‘Hot Key’
•
Power off the unit
•
Insert the factory programmed ‘Hot Key’ into the 5pin connecter
•
Power on the unit
•
Factory programmed parameters will be copied from “Hot Key” to controller
•
‘doL’ message will blink and then flashing ‘End’ will be shown on the LED.
•
After 10sec, unit will run with new parameters
•
Remove ‘Hot Key’ from electronic controller
Save Parameters in ‘Hot Key’
•
Power on the unit
•
Insert ‘Hot key’ and press
key
•
Factory programmed parameters will be copied to ‘Hot Key’
•
‘uPL’ message will blink and then flashing ‘End’ will be shown on the LED.
•
Press
key and ‘End’ will stop flashing
•
Power off unit and remove ‘Hot key’ from controller
•
Power on unit
Digital scroll compressor controller has been specially developed for Emerson ZXD condensing unit. This controller is only intended
for use in Emerson ZXD condensing units, therefore Emerson has no responsibility of any use on other condensing unit.