2. Reset the device and perform a new measurement.
Non-volatile memory defect
Alert
Non-volatile memory defect
Cause
The device has failed to access the non-volatile memory.
Recommended actions
1. Acknowledge the alert.
2. Reset the device.
3. Reconfirm all configuration items in the device.
Probe life reached 0%
Alert
Probe life reached 0%
Cause
The probe has reached end of life and needs to be replaced.
Recommended actions
1. Check the probe wiring and connections and perform a
measurement.
2. Inspect the probe and replace it, if necessary.
5.3.2
Troubleshooting – wireless network
•
Device not joining the network
•
•
•
Device not joining the network
Alert
Device not joining the network
Cause
Measurements are disabled.