11 – 18
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Blower Package PLC Operation Manual •Vilter/Emerson • 35391BLP
Status Messages and Blower State Indicator
Status messages are used to indicate blower status information to the user. Status messages are used to inform the
user of any of the following conditions.
• Anti-Recycle Timer is active
• Blower Package is in standby mode and is waiting for one or more conditions to be met
• Load Limits and Forced Unloading
• Blower PLC has automatically reverted to Local-Auto mode on loss of communications with central controller
or DCS (if this function is enabled)
• A user is logged in
• An output is forced
Status messages are shown in a green scrolling banner at the top of the overview and menu screens.
Figure 11-3. Alarm/Trip/Status Bars (Main Menu Screen)
Status Message
Notes
(S001) Status: Blower 1 Stopped
Displayed on the Event List only
(S002) Status: Blower 1 Started
Displayed on the Event List only
(S003) Status: Blower 2 Stopped
Displayed on the Event List only
(S004) Status: Blower 2 Started
Displayed on the Event List only
(S005) Status: Blower 3 Stopped
Displayed on the Event List only
(S006) Status: Blower 3 Started
Displayed on the Event List only
(S007) Status: Blower 4 Stopped
Displayed on the Event List only
(S008) Status: Blower 4 Started
Displayed on the Event List only
(S009) Status: Blower 1 Anti-Recycle
(S010) Status: Blower 2 Anti-Recycle
(S011) Status: Blower 3 Anti-Recycle
(S012) Status: Blower 4 Anti-Recycle
(S013) Status: Waiting to Start: Remote Run Permissive
Input
Blower PLC is waiting for a contact closure on the
remote run permissive input before the blowers may
start.
(S014) Status: Waiting to Start: Soft Run Permissive from
DCS/Central
Blower PLC is waiting for a run command from the
central controller or DCS (if control by communica-
tions enabled)
(S015) Status: Not Assigned
(S016) Status: Loading Inhibited: Low Suction Pressure
(S017) Status: Loading Inhibited: High Discharge Pressure
Table 11-3. Status Listing
Содержание Vilter PLC
Страница 1: ...Blower Package PLC Operation manual ...
Страница 2: ......
Страница 10: ...Blank TOC Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Страница 18: ...1 8 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Страница 30: ...3 2 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Страница 34: ...4 4 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Страница 42: ...5 8 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Страница 48: ...6 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Страница 54: ...7 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Страница 62: ...9 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Страница 68: ...10 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Страница 117: ......