34
Unidrive M400 User Guide
Issue Number: 2
Figure 4-4 Size 4 power connections
4.1.2 Ground connections
Size 1 to 4
On sizes 1 to 4, the supply and motor ground connections are made
using the ground busbar located at the bottom of the drive as shown in
Figure 4-5.
Figure 4-5 Size 1 to 4 ground connections (size 2 shown)
1
4 x M4 threaded holes for the ground connection busbar
Table 4-1 Protective ground cable ratings
L1
L2
L2
L1
L3
Optional EMC
filter
Optional
line reactor
Fuses
L3
Mains
Supply
Supply
Ground
PE
U
V
W
Motor
Optional ground
connection
+
BR
Optional
braking
resistor
Thermal
overload
protection
device
Internal
EMC
filter
Electrochemical corrosion of grounding terminals
Ensure that grounding terminals are protected against
corrosion i.e. as could be caused by condensation.
The ground loop impedance must conform to the
requirements of local safety regulations.
The drive must be grounded by a connection capable of
carrying the prospective fault current until the protective
device (fuse, etc.) disconnects the AC supply.
The ground connections must be inspected and tested at
appropriate intervals.
Input phase conductor size Minimum ground conductor size
≤
10 mm
2
Either 10 mm
2
or
two conductors of
the same cross-sectional area as the
input phase conductor.
> 10 mm
2
and
≤
16 mm
2
The same cross-sectional area as the
first input phase conductor.
> 16 mm
2
and
≤
35 mm
2
16 mm
2
> 35 mm
2
Half of the cross-sectional area of the
input phase conductor.
WARNING
1
WARNING