Type RP
11
Figure 6.
RP Series Regulator (continued)
LM/1391
OUTLET PRESSURE > 2 BAR VERSION
48
47
51
50
49
61
69
68
34
VERSION WITHOUT SLAM-SHUT
646362
67
6566
FLANGED VERSION
Страница 1: ...1 66 This product has been designed to be used with fuel gases of 1st and 2nd family according to EN 437 and with other non aggressive and non fuel gases For any other gases other than natural gas please contact your local sales agent The following versions are available RP 011 RP 022 RP 033 Regulator RP 011 66 RP 022 66 RP 033 66 Regulator with slam shut The standard gas pressure devices regulato...
Страница 2: ...nections RP 011 1 x 1 1 4 BSP RP 022 1 1 4 x 2 BSP RP 033 2 x 3 BSP Flanged Connections RP 011 FS DN 25 x 32 PN 16 25 40 CL150 CL300 RP 022 FS DN 32 x 50 PN 16 25 40 CL150 CL300 RP 033 FS DN 50 x 80 PN 16 25 40 CL150 CL300 Warning The pressure temperature limits indicated in this instruction manual or any applicable standard or code limitation should not be exceeded Maximum Operating Inlet Pressur...
Страница 3: ...any possible external ignition source inside the equipment due to mechanical generated sparks drainage to safe area via drain lines of foreign materials if any by inflow of fuel gas with low velocity in the pipe work 5m sec In any case provisions of Directive 1999 92 EC and 89 655 EC shall be enforced by gas pressure regulating measuring station installation s end user with a view to preventing an...
Страница 4: ...Inlet Outlet RP 011 1 1 1 4 50 280 120 206 102 135 185 195 6 5 RP 011 66 1 1 1 4 280 120 206 102 135 185 195 125 7 7 RP 022 1 1 4 2 50 300 120 266 106 135 185 200 10 5 RP 022 66 1 1 4 2 300 120 266 106 135 185 200 125 11 7 RP 033 2 3 70 300 120 266 120 160 230 270 13 RP 033 66 2 3 300 120 266 120 160 230 270 142 14 2 I1 Flanged connections PN 16 25 40 I2 Flanged connections CL 300 DIMENSIONS and w...
Страница 5: ...he valve disc the antagonist action of the adjustment springs tends to open it Under normal conditions the balance between these antagonist actions positions the valve disc in such a way as to ensure a constant pressure and therefore the downstream capacity Upon any capacity variation tending to cause an increase or decrease of pressure in relation to the pre set pressure the moving unit reacts an...
Страница 6: ...id standards the gas shall be cleaned by proper filters separators scrubbers to avoid any technical reasonable hazard of erosion or abrasion for pressure containing parts Pressure equipment in subject shall be installed in non seismic area and hasn t to undergo fire and thunderbolt action Clean out all pipelines before installation of the regulator and check to be sure the regu lator has not been ...
Страница 7: ...ndustry codes standards and regulations recommendations In accordance with applicable National or Industry codes standards and regulations recommendations all hazards covered by specific tests after final assembling before applying the CE marking shall be covered also after every subsequent reassembly at installation site in order to ensure that the equipment will be safe throughout its intended l...
Страница 8: ... Check for leaks using suds Spare parts Spare parts storage shall be done by proper procedures according to national standard rules to avoid over aging or any damage Troubleshooting Table 3 General Troubleshooting for RP Series SYMPTOMS Cause ACTIONS The regulator does not open Lack of incoming gas Check the station feeding The slam shut controller has not been reset Manually reset the slam shut c...
Страница 9: ...g 37 Filter 38 Seta 39 O ring 40 Body 41 Gasket 42 Lower cover 43 Pin 44 Nut 45 Washer 46 Gasket 47 Diaphragm 48 Screw 49 Plate 50 Plate 51 Plate 52 Screw 53 Washer 54 Support 55 Lever 56 Needle 57 Needle 58 Fork lever 59 Label 60 Screw 61 Plate 62 O ring 63 Hub 64 Flange 65 Flange 66 Hub 67 O ring 68 Plug 69 Plug Rubber parts marked with are supplied in the spare parts kit recommended as stock To...
Страница 10: ...Type RP 10 Figure 6 RP Series Regulator continued LM 1391 59 58 57 56 55 60 54 53 52 ...
Страница 11: ...Type RP 11 Figure 6 RP Series Regulator continued LM 1391 OUTLET PRESSURE 2 BAR VERSION 48 47 51 50 49 61 69 68 34 VERSION WITHOUT SLAM SHUT 64 63 62 67 65 66 FLANGED VERSION ...
Страница 12: ...ers McKinney Texas 75070 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9000 Europe Bologna 40013 Italy Tel 39 051 419 0611 Middle East and Africa Dubai United Arab Emirates Tel 971 4811 8100 For further information visit www emersonprocess com regulators Natural Gas Technologies Emerson Process Management Regulator Technologies Inc USA Headquar...