6 0 LCD Screen Diagnostics

Operation and Overview of LCD Panel

UPS Power On

To turn on the UPS unit, press the ON/OFF button 
lightly for 2 seconds then the LCD will display on.

UPS Power Off

To turn off the UPS unit, press the ON/OFF button 
lightly for 2 seconds then the LCD will display off.

AC Start Mode

AC start mode, the back light will flash once every 
0.5 second.

Line and AVR Mode

AVR mode, the bottom icon will flash once every  
0.5 second.

Page: 6

4.0 Interface

operation and overview of LCD Panel

 Operation Mode

 Status

 Load and Battery capacity

 Number will be displayed in the 

following order Vin, Vo, load, battery 
capacity

UPS Power on

To turn on the UPS unit, press the power switch SW2 
lightly for 2 seconds then the LCD will display on.

UPS Power off

To turn off the UPS unit, press the power switch SW2 
lightly for 3 seconds then the LCD will display off.

AC Start Mode

AC start mode, the back light will flash once every 
0.5 second

Line and AVR Mode

AVR mode, the 

bottom

 icon will flash once 

every 0.5 

second.

Battery Mode

Low Battery

Battery voltage low, the battery alarm icon will flash 
once every 0.5 second.

SSW UPS

 

Rev.

3

 2019/0

5

/30

Содержание SSW Series

Страница 1: ...Uninterruptible Power Supply User Manual SSW UPS Series ...

Страница 2: ...tant Safety Instructions 2 3 0 General Description 3 4 0 System Block Diagrams 5 5 0 Installation and Operation 6 6 0 LCD Screen Diagnostics 7 7 0 Battery Replacement 10 8 0 Troubleshooting 15 9 0 Technical Specifications 16 Technical Support 18 Warranty 18 ...

Страница 3: ...nication Port on the rear panel of the UPS Please visit www solahd com for more information 1 0 Introduction Thank you for selecting the SSW Uninterruptible Power System This manual contains important safety instructions that should be folllowed during the installation and operation of your UPS Please read all safety installation and operating instructions before attempting to install or operate t...

Страница 4: ...ily disconnected To properly turn off the UPS press the ON OFF button for three 3 seconds then disconnect the input power supply cord from the AC power outlet Connect the AC input power cord to a properly grounded AC supply source Connect the UPS to a grounded supply circuit with proper branch circuit protection Follow all applicable National Electrical Codes NEC and Canadian Electrical Codes CEC ...

Страница 5: ...s and the LCD will display UPS status To turn the UPS off press the ON OFF button for two 2 seconds and LCD display will shut off Setup Button When you press the setup button the LCD screen will display the functions below in the following sequence Input Voltage V Input Frequency Hz Output Voltage V Output Frequency Hz Output Load Output Load kVA Battery Voltage Battery Voltage V ...

Страница 6: ...rt RJ 45 Surge Input Cable Breaker Site Fault Indicator Receptacles Protection Rear View of SSW700 and SSW1000 USB Port RJ 45 Surge Input Cable Breaker Site Fault Indicator Receptacles Optional SNMP Protection Rear View of SSW1500 ...

Страница 7: ...Page 5 4 0 System Block Diagrams SSW700 and 1000 System Block Diagram SSW1500 System Block Diagram ...

Страница 8: ... the battery for eight 8 hours before initial use 5 5 Turn On the UPS Press the ON OFF button for 2 seconds 5 6 Set Up Audible Alarm On Off When the UPS powers on the audible alarm may sound The steps below outline how to turn the audible alarm on or off Step1 Press and hold the ON OFF button for three 3 seconds to set up audible alarm ON OFF Step2 Press the setup button once to set up audible ala...

Страница 9: ...operation and overview of LCD Panel Operation Mode Status Load and Battery capacity Number will be displayed in the following order Vin Vo load battery capacity UPS Power on To turn on the UPS unit press the power switch SW2 lightly for 2 seconds then the LCD will display on UPS Power off To turn off the UPS unit press the power switch SW2 lightly for 3 seconds then the LCD will display off AC Sta...

Страница 10: ...tops to provide power and the battery alarm icon will flash once every 0 5 second Battery Voltage Over Charge Battery voltage over charge the battery alarm icon will flash once every 0 5 second and display HI Short for Line and AVR Mode LCD display SP when UPS operates in LINE or AVR mode Short for Battery Mode LCD display SP when UPS operates in battery mode ...

Страница 11: ...erload limit the setup button will be locked OverLoad 110 for Battery Mode When the UPS is within the overload limit the alarm icon will flash once every 0 5 seconds When the UPS is beyond the overload limit the setup button will be locked Over Temperature for Line and AVR Mode Over Temperature for Battery Mode Setup Audible Alarm On Setup Audible Alarm Off ...

Страница 12: ...atings Do not open or damage the battery Released electrolyte is harmful to the skin and eyes and may be toxic A battery presents a risk of electrical shock and high short circuit current The following precautions should be adhered to when replacing the batteries 1 Remove watches rings or any other metal objects from the hands 2 Use tools with insulated handles 3 Wear rubber gloves and boots 4 Do ...

Страница 13: ...e corners of the front plate Step 2 Place the faceplate on top of the UPS for easy access to the battery connections Step 3 First disconnect the red connector positive then disconnect the black ground connector from the battery pack Step 4 Using a Phillips head screwdriver remove the four 4 silver screws from the silver battery pack retaining plate ...

Страница 14: ... between the battery packs Step 7 After completing the previous steps the result should resemble the image above Step 8 Be sure to dispose of the batteries properly at a recycling center If you need assistance please contact technical support They will assist you in finding the closest battery recycling center to your location ...

Страница 15: ...ners of the front plate Step 2 Place the faceplate on top of the UPS for easy access to the battery connections Step 3 First disconnect the red connector positive then disconnect the black ground connector from the battery pack Step 4 Using a Phillips head screwdriver remove the four 4 silver screws from the silver battery pack retaining plate ...

Страница 16: ...onnect the battery wire then disconnect the jumper wires Step 7 After completing the previous steps the result should resemble the image above Step 8 Be sure to dispose of the batteries properly at a recycling center If you need assistance please contact technical support They will assist you in finding the closest battery recycling center to your location ...

Страница 17: ...Remove some unnecessary loads Before reconnecting equipment Please verify that the load matches the UPS capability specified in specs Battery defect Replace the battery UPS fault or charger failure Contact Tech Support Fault code displayed Overload Remove some unnecessary loads Before reconnecting equipment Please verify that the load matches the UPS capability specified in specs UPS short circuit...

Страница 18: ...conds at 130 5 power will not be provided to the load Then every 10 minutes auto recovery will be attempted Short Circuit 1 The output current continues over 125 within 60ms to OSCP and then goes to Battery Mode 2 UPS goes to retry mode every 10 seconds until Battery Voltage VB 11V cell 3 The battery recharges when the VB 12 7V cell then UPS continues retry mode every 10 seconds 4 UPS goes into au...

Страница 19: ...e approximate Based on new fully charged standard batteries at a temperature of 25 C 77 F with 100 resistive UPS loading Run times listed above can vary by 5 due to manufacturing variances of the batteries Catalog Number Dimensions H x W x D in mm SSW700 9 09 x 6 69 x 12 4 231 x 170 x 315 SSW1000 9 09 x 6 69 x 12 4 231 x 170 x 315 SSW1500 9 09 x 6 69 x 16 97 231 x 170 x 431 ...

Страница 20: ...rt Website www solahd com Technical Support E Mail solahd technicalservices emerson com Toll Free 800 377 4384 USA 847 268 6651 Warranty Please see the Terms Conditions of Sale document within the UPS packaging While every precaution has been taken to ensure accuracy and completeness in this manual Appleton Grp LLC d b a Appleton Group assumes no responsibility and disclaims all liability for dama...

Страница 21: ...ndustriel Nord 35 rue André Durouchez CS 98017 80084 Amiens Cedex 2 France T 33 3 2254 1390 China Sales Office Shanghai T 86 21 3338 7000 Canada EGS Electrical Group Canada Ltd 99 Union Street Elmira ON N3B 3L7 Canada T 1 888 765 2226 Middle East Sales Office Dammam Saudi Arabia T 966 13 510 3702 Chile Sales Office Las Condes T 56 2928 4819 India Sales Office Chennai T 91 44 3919 7300 Korea Sales ...

Отзывы: