UL 1283 Required Language Concerning the Installation of EMI Filters 
(Standard on SPD200K/300K)

A.  An insulated grounding conductor that is identical in size and insulation material and thickness to the 

grounded and ungrounded circuit supply conductors, except that it is green with or without one or more 

yellow stripes, is to be installed as part of the circuit that supplies the filter. Reference should be made to 

Table 250-122 of the National Electrical Code regarding the appropriate size of the grounding conductor.

B.  The grounding conductor mentioned in item a is to be grounded at the service equipment or other 

acceptable building ground such as the building frame in the case of a high-rise steel frame structure.

C. 

Any attachment-plug receptacles in the vicinity of the filter are to be of a grounding type, and the 

grounding conductors serving these receptacles are to be connected to ground at the service equipment 
or other acceptable building ground such as the building frame in the case of a high-rise steel-frame 
structure.

D. 

Pressure terminal or pressure splicing connectors and soldering lugs used in the installation of the filter 
shall be identified as being suitable for the material of the conductors. Conductors of dissimilar metals 

shall not be intermixed in a terminal or splicing connector where physical contact occurs between 

dissimilar conductors unless the device is identified for the purpose and conditions of use.

Operation

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Apply appropriate personal protective equipment (PPE) and follow safe  electrical work practices. See NFPA 70E, 

CSA Z462 or NOM-029-STPS.

• 

This equipment must only be installed and serviced by qualified electrical personnel.

• 

Turn off all power supplying this equipment before working on or inside equipment.

• 

Always use a properly rated voltage sensing device to confirm power is off.

• 

Replace all devices, doors and covers before turning on power to this equipment.

• 

This equipment must be effectively grounded per all applicable codes. Use an equipment-grounding conductor to 

connect this equipment to the power system ground.

Failure to follow these instructions will result in death or serious injury.

LED Status Indicators

The SPD diagnostic display panel shows the status of each phase of the SPD  with diagnostically controlled 
green/red LEDs). If a unit is operating correctly, all of the phase LEDs will be illuminated green. To test the 
integrity of the diagnostics for each phase, push the button below the phase LEDs on the diagnostic display 
panel. The green LED will turn red and the alarm will sound, if the alarm is enabled. Releasing the test button 
will complete the test; the red LED will turn green and the alarm will shut off.

If an inoperable condition occurs on any phase, the audible alarm sounds and the corresponding phase LED on 
the diagnostic display panel is extinguished and the service light will illuminate. This indicates that the device 

needs service by qualified electrical personnel.

The audible alarm can be silenced, until a qualified person is able to evaluate and service the SPD, by pressing 

the alarm silence button. The alarm will silence and the LED above the buttom will be lit. The red service LED 
will continue to be illuminated until the inoperative condition had been cleared.

Содержание SolaHD SPD200K Series

Страница 1: ...Surge Protective Devices SPD200K 300K Series ...

Страница 2: ...jury or death DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE NOTICE is used to address practices not related to phy...

Страница 3: ...ia to cause birth defects or other reproductive harm For more information go to www P65Warnings ca gov NOTICE LOSS OF BRANCH CIRCUIT POWER LOSS OF SURGE SUPPRESSION Perform periodic inspection of the surge protective device status indicator lights as part of the preventative maintenance schedule Promptly replace the surge protective device when an alarm state exists Use dry contacts to signal an a...

Страница 4: ...Replace all devices doors and covers before turning on power to this equipment This equipment must be effectively grounded per all applicable codes Use an equipment grounding conductor to connect this equipment to the power system ground Failure to follow these instructions will result in death or serious injury Proper installation is imperative to maximize the SolaHD SPD200K 300K s effectiveness ...

Страница 5: ...all according to UL 1449 test standards Electrical Voltage Rating DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Confirm the SPD voltage rating on the module or nameplate label is not less than operating voltage the operating voltage Failure to follow these instructions will result in death or serious injury Prior to mounting the SPD verify that the device has the same voltage rating as th...

Страница 6: ...0kA 120 208V Internal Rotary Disconnect and LED s Audible Alarm Relay Surge Counter Available Part Number Combinations PARALLEL SPDs PARALLEL SPDs SPD200K10YRC SPD300K10YRC SPD200K27YRC SPD300K27YRC SPD200K24DRC SPD300K24DRC SPD200K48DRC SPD300K48DRC SPD200K34YRC SPD300K34YRC SPD200K60DRC Figure 1 DELTA HRG WYE Figure 2 WYE Phase A Black Phase C Black Phase B Black Ground Green V Phase A Black Pha...

Страница 7: ...ure 3 Figure 3 Surge Protective Device Wiring Practice To load s Phases Neutral Ground Ground bus Neutral bus SPD Phase A Phase B Phase C Neutral Ground Panel Interconnect wiring Minimize length Avoid sharp bends Grounding DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Connect the Surge Protective Device ground terminal to the building grounding grid structure Use an appropriately sized eq...

Страница 8: ...roper over voltage suppression by this SPD use a single point ground system where the service entrance grounding electrode system is connected to and bonded to all other available electrodes building steel metal water pipes driven rods etc for reference see IEEE 142 2007 The ground impedance measurement of the electrical system should be as low as possible and in compliance with all applicable cod...

Страница 9: ...stem and to adjust the grounding resistance accordingly As the power system is modified the value of the grounding resistor must be evaluated and adjusted to maintain the system in the over damped state Installation DANGER HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Apply appropriate personal protective equipment PPE and follow safe electrical work practices See NFPA 70E CSA Z462 or NOM 029 ST...

Страница 10: ...nt before working on or inside equipment Always use a properly rated voltage sensing device to confirm power is off Replace all devices doors and covers before turning on power to this equipment This equipment must be effectively grounded per all applicable codes Use an equipment grounding conductor to connect this equipment to the power system ground Confirm the SPD voltage rating on the module o...

Страница 11: ...refer to the section Dry Contacts on page 14 for wiring instructions 7 Replace all devices doors and covers before turning on power to the equipment If the SPD is properly installed and functioning the green LED indicators on the display will be lit and the service LED extinguished If you have any questions pertaining to the installation of this device contact us at 1 800 377 4384 or solahd techni...

Страница 12: ...10 AWG wire A 2 1 3 4 6 5 7 8 B C N A B C N A B N C G THREE POLE C N G A TWO POLE 2 1 3 4 6 5 7 8 G C B N A THREE POLE W DS N G B SINGLE POLE C N G B A THREE POLE SPD PHASE C PHASE A PHASE B NEUTRAL GROUND N A B C Wiring Diagrams With Disconnect Switch NOTICE HAZARD OF LOSS OF PROPERLY FUNCTIONING LED ALARM STATUS Bond the ground and neutral lugs with a 10 AWG wire when connected to no neutral pow...

Страница 13: ...conductor The neutral conductor is not present on Delta systems Phase B of the electrical system is typically the grounded phase A B C N A B C N THREE POLE C N G A TWO POLE 2 1 3 4 6 5 7 8 G C B A THREE POLE W DS N B GLE POLE N B A EE POLE SPD Ground Phase B Phase C Phase A B A C Corner Grounded Delta SPD Ground Phase B Phase C Phase A B A C Ungrounded Delta ...

Страница 14: ...ective equipment PPE and follow safe electrical work practices See NFPA 70E CSA Z462 or NOM 029 STPS This equipment must only be installed and serviced by qualified electrical personnel Turn off all power supplying this equipment before working on or inside equipment Always use a properly rated voltage sensing device to confirm power is off Replace all devices doors and covers before turning on po...

Страница 15: ...is illuminated Surge Counter Count Increments optional surge counter by one 1 Surge Counter Reset Resets optional surge counter to zero 0 Audible Alarm Push the alarm silence button to enable or disable the alarm see Figure 6 If the service LED is lit the alarm is enabled If the service LED is not lit the alarm is disabled Surge Counter The surge counter displays the number of transient voltage su...

Страница 16: ...nections In the unpowered state the contact is closed between terminals NC and COM This is also the alarm condition The opposite state closed between terminals NO and COM indicates that power is on to the unit and that no alarm condition exists Figure 7 Dry Contact Option NO DRY CONTACTS NCNC C NO C These contacts can be used for remote indication of the SPD s operating status to a computer interf...

Страница 17: ...ly to help maintain system performance and continued transient voltage surge suppression Periodically check the state of the diagnostic display panel LED status indicators Routinely use the built in diagnostics to inspect for inoperative modules Troubleshooting This surge protector has little to troubleshoot If a phase LED in extinguished or the service light is on please contact us For applicatio...

Страница 18: ...SPD200K 300K Page 16 ...

Страница 19: ...84 USA 847 268 6651 Warranty Please refer to the Terms Conditions of Sale document While every precaution has been taken to ensure accuracy and completeness in this manual Appleton Grp LLC d b a Appleton Group assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions ...

Страница 20: ...ustriel Nord 35 rue André Durouchez CS 98017 80084 Amiens Cedex 2 France T 33 3 2254 1390 China Sales Office Shanghai T 86 21 3338 7000 Canada EGS Electrical Group Canada Ltd 99 Union Street Elmira ON N3B 3L7 Canada T 1 888 765 2226 Middle East Sales Office Dammam Saudi Arabia T 966 13 510 3702 Chile Sales Office Las Condes T 56 2928 4819 India Sales Office Chennai T 91 44 3919 7300 Korea Sales Of...

Отзывы: