Page: 9
SPD200K/300K
4. Install in accordance with national and local electrical codes for overcurrent protection recommendations
and wire ampacity considerations.
Note: Use on solidly grounded systems unless the SPD model is designed for installation on ungrounded
/HRG systems.
Note: See “Terminals, Wire Size, and Installation Torque” and Table 2 on page 5 for acceptable wire size and
installation torque.
5. Twist conductors 1/2 turn or more for every twelve inches of length. Do not loop or coil wires. Be sure to
maintain adequate wire bending space per NEC.
6. If the remote signaling contacts of the diagnostic display panel are to be used, refer to the section, “Dry
Contacts,” on page 14 for wiring instructions.
7. Replace all devices, doors, and covers before turning on power to the equipment. If the SPD is properly
installed and functioning, the green LED indicators on the display will be lit and the service LED
extinguished.
If you have any questions pertaining to the installation of this device, contact us at 1-800-377-4384
or [email protected].
Dimensions and Weights
Model
H/W/D (in. / mm.)
Weight
SPD200K / SPD300K
12" x 12" x 6" (305 x 305 x 152)
23 lbs (10.4 kg)
Figure 8: Typical Panel Installation
When breaker connecting, use
closest breaker to SPD
Locate SPD close
to intended breaker
Keep Leads Short as Possible
Avoid Sharp Bends
Outdoor installation requires
appropriate weather sealing
at nipple (gasket, sealing
conduit, etc.)
To Protected Loads
A
B
C
G
N
BREAKER