1.3 Environmental 

Ratings 

1.3.1  Operating Ambient Temperature Range:

  -20°C to +65°C (-4°F to +149°F). 

1.3.2  Storage Ambient Temperature Range:

  -40°C to +85°C (-40°F to +185°F). 

1.3.3 Humidity:

  This DC-DC Converter System is capable of operating in an ambient relative 

humidity range of 0 to 95%, non-condensing. 

1.3.4 Altitude:

  The maximum operating ambient temperature should be derated by 10°C at an 

elevation of 10,000 feet.  For elevations between sea level and 10,000 feet, derate the maximum 
operating ambient temperature linearly. 

1.3.5 Ventilation 

Requirements:

  Each Converter Module is fan cooled, using front to back 

ventilation.  The Converter Mounting Shelf must be located such that ventilation openings are 
not blocked and temperature of the air entering the cabinet is not above or below the Operating 
Ambient Temperature Range stated in this document. 

1.3.6 Heat 

Dissipation:

  16.98 Watts per square foot / foot maximum. 

1.3.7 Audible 

Noise:

  With three Converter Modules installed and operating, the audible noise at any 

point 5 feet from any vertical surface of the equipment shelf does not exceed 60 dBA when 
measured with a sound level meter conforming to ANSI S1.4. 

1.3.8 EMI/RFI 

Suppression:

  This DC-DC Converter System conforms to the requirements of FCC 

rules Part 15, Subpart B, Class B, for radiated and conducted noise. 

1.3.9 Filtering: 

 

Noise reflected back to the central office battery is within the parameters set forth in 

Telcordia Technical Reference TR-TSY-000009, paragraph 5.0, using test measurements in 
Telcordia Technical Reference PUB 43802, pages 5 and 6. 

1.3.10 Compliance Information: 

(A) Safety Compliance:

  This unit meets the requirements of UL 1950, Standard for Information 

Technology Equipment, and is UL Recognized as a power supply for use in Telephone, 
Electronic Data Processing or Information Processing Equipment.  This unit meets the 
requirements of CSA 22.2, No. 950 and is tested and Certified by UL ("c UR") as a 
Component Type Power Supply. 

1.3.11 Mounting:

  This product is intended only for installation in a Restricted Access Location on or 

above a non-combustible surface. 

This product must be located in a Controlled Environment with access to Craftspersons only. 

This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut, 
or other environmentally controlled electronic equipment enclosure). 

This product is intended to be connected to the common bonding network in a Network 
Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic 
equipment enclosure). 

1.4 Standard 

Features 

1.4.1  Type of Power Conversion Circuit:

  High Frequency. 

1.4.2 Input 

Protection: 

(A) Fusing:  

A 35-ampere non-user replaceable fuse is located in the positive input lead of each 

Converter Module. 

(B)  Low Input Voltage Inhibit:

  Operation of the Converter Modules will inhibit if the input 

voltage drops to within the range of 19.25 to 20.5 volts.  While operation is inhibited, the 
Converter Shelf will draw no more than 20 mA.  Operation will automatically resume after the 
input voltage returns to within normal operating limits. 

Содержание SAG584622000

Страница 1: ... to mount in a 19 or 23 nominal relay rack or equipment mounting rack configured for 19 mounting unless otherwise specified The Converter Module Mounting Shelf when equipped with up to three separately ordered Converter Modules Spec No 486800127 provides a DC DC Converter System that operates from 24VDC to provide 48VDC load power Spec No 584622000 Model DCS4830 Input Voltage 24 Volts DC Output Vo...

Страница 2: ...c is strictly prohibited TABLE OF CONTENTS System Overview Ordering Information Specifications Physical Size Information Related Documentation SYSTEM OVERVIEW 1 TABLE OF CONTENTS 2 ORDERING INFORMATION 3 Converter Module Mounting Shelf Model DCS4830 3 Converter Modules Model MHSA10B 3 Wiring Notes 4 DC Input 24V 4 DC Output 48V 5 External Control and Alarms 6 Wiring Illustrations 7 DC Input 24V 7 ...

Страница 3: ...Mounting Shelf Model DCS4830 Features The Converter Module Mounting Shelf accepts up to three 3 DC DC Converter Modules Two 2 blank panels are provided to cover unused Converter Module mounting positions 19 rack mounting angles factory installed 23 rack mounting angles supplied loose can be adjusted for a 5 or 6 front projection Ordering Notes 1 For each DC DC Converter System specify 1 Spec No 58...

Страница 4: ...tion refer to drawings 031110100 through 031110300 2 Customer must provide 1 4 20 hardware to secure lugs to DC input busbars Recommended Crimp Lug 3 Recm 90 C Wire Size 1 AWG Loop Length 2 feet Vendor Part No T B 54206 Burndy YA4CL 2TC14 4 47 Emerson 245346800 T B 54207 Burndy YA2CL 2TC14 2 74 Emerson 245346900 T B Burndy YA25L 2TC14 1 0 118 9 Emerson 245391400 1 Wire sizes based on recommendatio...

Страница 5: ...SI approved National Fire Protection Association s NFPA National Electrical Code NEC and applicable local codes When used for power distribution load should not exceed 80 of device rating except 10 and 15 ampere fuses for which load should not exceed 70 of device rating Terminal block wire size capacity is 24 to 14 AWG Each GMT Fuse Module has a 30A 65 C 149 F maximum capacity combined load of bot...

Страница 6: ...ohibited Home External Control and Alarms Features An external control and alarm circuit card is located behind the shelf s top front access panel This circuit card provides three sets of Form C relay contacts for external alarms plus an ESTOP input A terminal block is provided on the circuit card for customer connections Restrictions Terminal block wire size capacity is 14 to 26 AWG Relay contact...

Страница 7: ...r Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Home Wiring Illustrations DC Input 24V Front Cover Captive Fasteners DC Input Terminals Located Behind Insulating Shield bend shield up to access terminals Top Cover w insulating shield removed in illustration for cla...

Страница 8: ...l and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Home DC Output 48V Front Door Captive Fastener DC Output Leads Enter Here DC Output Terminal Blocks 48V Distribution Leads Load Return Leads Front View DC Out...

Страница 9: ...rk Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Home External Control and Alarms Front Cover Captive Fasteners External Control and Alarm Terminal Block ESTOP NC C NO All relay contacts are shown in the deenergized state Relays are deenergized when in the al...

Страница 10: ...atic Steady state output voltage remains within 1 volt of the pre adjusted voltage for any load current from no load to full load and over the specified input voltage range B Dynamic For a step load change of 50 within the range of 10 to 100 of full rated current the maximum voltage transient will not exceed 5 of the initial steady state voltage 1 1 4 Filtering With at least 10 of rated full load ...

Страница 11: ...28 volts DC 1 2 2 Filtering Noise reflected back to the central office battery is less than 32 dBrnC 1 2 3 Typical Input Data When equipped with one Converter Module A The output voltage of the DC DC Converter Module is initially adjusted to 48 volts at 50 load and 24 volts DC input Input Voltage Percent of Full Load Input Current Amps Efficiency Typical Heat Dissipation BTU Hr 0 0 84 60 25 6 99 8...

Страница 12: ...me 1 2 4 Typical Input Data When equipped with three Converter Modules A The output voltage of the DC DC Converter Modules are initially adjusted to 48 volts at 50 load and 24 volts DC input Input Voltage Percent of Full Load Input Current Amps Efficiency Typical Heat Dissipation BTU Hr 0 2 42 173 25 20 90 82 3 265 50 39 59 86 4 385 75 59 09 86 4 575 21 VDC 100 79 23 85 4 828 0 2 12 174 25 18 45 8...

Страница 13: ...erter System conforms to the requirements of FCC rules Part 15 Subpart B Class B for radiated and conducted noise 1 3 9 Filtering Noise reflected back to the central office battery is within the parameters set forth in Telcordia Technical Reference TR TSY 000009 paragraph 5 0 using test measurements in Telcordia Technical Reference PUB 43802 pages 5 and 6 1 3 10 Compliance Information A Safety Com...

Страница 14: ...dancy 1 4 5 External Alarm Circuits A set of Form C relay contacts is provided for each of the following alarms Relays are energized for normal operating conditions and de energized for an alarm condition Refer also to the Wiring Notes and Wiring Illustrations section in this document and to the DC DC Converter System Installation and User Instructions Section 6035 for wiring information A Convert...

Страница 15: ...t without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Home PHYSICAL SIZE INFORMATION Overall Dimensions 17 37 12 18 6 00 note 4 Top View Front View Left Side View Right Side View Mounting Angle Detail Notes 1 All dimensions are in inches unless otherwise specified 2 Weight in LBS Shelf Net 17 Shipping 21 Converter Net 3 2 Shipping 5 3 Fin...

Страница 16: ...and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Home RELATED DOCUMENTATION Schematic Diagram SD584622000 Wiring Diagram T584622000 Installation and User Instructions Section 6035 ...

Страница 17: ... Energy Systems North America Inc is strictly prohibited Home REVISION RECORD Issue Change Number ECO Description of Change Date Approved AA LLP213133 New 10 22 09 John Jasko AB LLP213431 Maximum heat dissipation value added 11 18 09 John Jasko Emerson Network Power Energy Systems North America Inc 1122 F Street Lorain Ohio 44052 2293 440 288 1122 In Canada Emerson Network Power Canada 363 Soverei...

Отзывы: