Removing the detector for maintenance purposes does not require removing the
tilt mount.
2. Place the detector with its conduit/cable inlets pointing downwards on the detector
holding plate of the tilt mount.
3. Secure the detector with M10 x 1.5 screws with number M10 spring washers.
4. Secure the detector to the tilt mount using hex key number 7 for M10 x 1.5 screws.
5. Repeat steps
5.7
Install detector wiring
Procedure
1. Release the back cover secure bolt and open the detector back cover.
The chamber is now revealed.
Figure 5-5: Detector with Cover Removed
A. Housing
B. Terminal board
C. Inlet conduit
D. Detector holding plate
E. Earth terminal
F. Connection to Field Communicator
2. Remove the protective plug mounted on the detector conduit/cable entry inlet.
3. Pull the wires through the detector inlet conduit.
Installation
Reference Manual
October 2021
00809-0100-4036
44
Emerson.com/Rosemount
Содержание Rosemount 936
Страница 1: ...Reference Manual 00809 0100 4036 Rev AD October 2021 Rosemount 936 Toxic Open Path Gas Detector ...
Страница 4: ...4 ...
Страница 8: ...Product overview Reference Manual October 2021 00809 0100 4036 8 Emerson com Rosemount ...
Страница 24: ...Operating modes Reference Manual October 2021 00809 0100 4036 24 Emerson com Rosemount ...
Страница 30: ...Specifications Reference Manual October 2021 00809 0100 4036 30 Emerson com Rosemount ...
Страница 50: ...Installation Reference Manual October 2021 00809 0100 4036 50 Emerson com Rosemount ...
Страница 68: ...Wiring configurations Reference Manual October 2021 00809 0100 4036 68 Emerson com Rosemount ...
Страница 72: ...Support Reference Manual October 2021 00809 0100 4036 72 Emerson com Rosemount ...
Страница 74: ...Short range model Reference Manual October 2021 00809 0100 4036 74 Emerson com Rosemount ...