Power consumption
Table B-2: Detector and source maximum power consumption
Without heated optics
(maximum)
With heated optics
(maximum)
Detector
150 mA
300 mA
Source
200 mA
300 mA
Electrical input protection
The input circuit is protected against voltage-reversed polarity, voltage transients, surges,
and spikes, according to EN50270.
Electrical outputs
•
0-20 mA current output: The 0-20 mA is an isolated sink option. You can also configure
this output as source.
The maximum permitted load resistance is 500 Ω.
•
Communication network: The detector is equipped with an RS-485 communication
link that can be used in installations with computerized controllers.
Communication is compatible with the Modbus
®
protocol.
—
This protocol is standard and widely used.
—
It enables continuous communication between a single standard Modbus controller
(master device) and a serial network of up to 247 detectors.
—
It enables connection between different types of Rosemount detectors or other
Modbus devices to the same network.
•
HART
®
protocol: A digital communication protocol used to communicate between
intelligent field instruments and the host system.
Through the HART protocol, the detector can:
—
Display setup.
—
Reconfigure setup.
—
Display and determine the detector status.
—
Perform detector diagnostics.
—
Troubleshoot.
B.2.1
Power consumption
Table B-3: Detector and Source Maximum Power Consumption
Without heated optic (max.)
With heated optic (max.)
Detector
200 mA
250 mA
Source
200 mA
250 mA
Specifications
Reference Manual
May 2022
00809-0100-4035
58
Emerson.com/Rosemount
Содержание Rosemount 935
Страница 1: ...Reference Manual 00809 0100 4035 Rev AH May 2022 Rosemount 935 Open Path Combustible Gas Detector ...
Страница 8: ...Product overview Reference Manual May 2022 00809 0100 4035 8 Emerson com Rosemount ...
Страница 16: ...Technical description Reference Manual May 2022 00809 0100 4035 16 Emerson com Rosemount ...
Страница 22: ...Operating modes Reference Manual May 2022 00809 0100 4035 22 Emerson com Rosemount ...
Страница 46: ...Operation Reference Manual May 2022 00809 0100 4035 46 Emerson com Rosemount ...
Страница 48: ...10 Do a functional check Maintenance Reference Manual May 2022 00809 0100 4035 48 Emerson com Rosemount ...
Страница 52: ...Troubleshooting Reference Manual May 2022 00809 0100 4035 52 Emerson com Rosemount ...
Страница 56: ...Ordering information Reference Manual May 2022 00809 0100 4035 56 Emerson com Rosemount ...
Страница 62: ...Specifications Reference Manual May 2022 00809 0100 4035 62 Emerson com Rosemount ...
Страница 70: ...Wiring configurations Reference Manual May 2022 00809 0100 4035 70 Emerson com Rosemount ...
Страница 74: ...Support Reference Manual May 2022 00809 0100 4035 74 Emerson com Rosemount ...