Figure 5-4: Magnetic mode selector
A. Magnet
To switch from each position (
through
®
, or
RS-485 or move the magnetic mode selector above the magnetic switch (see
Procedure
1. Switch from Normal to Alignment mode.
2. Switch from Alignment to Standby mode.
3. Switch from Standby to Zero Calibration mode.
The 0-20 mA output should now be at 1 mA.
4. Wait up to sixty seconds until it switches to Normal mode.
The detector reading is now set to Normal. The 0-20 mA output should now
indicate 4 mA.
Postrequisites
Once zero calibration is complete, refer to
parameters.
Operation
Reference Manual
May 2022
00809-0100-4035
44
Emerson.com/Rosemount
Содержание Rosemount 935
Страница 1: ...Reference Manual 00809 0100 4035 Rev AH May 2022 Rosemount 935 Open Path Combustible Gas Detector ...
Страница 8: ...Product overview Reference Manual May 2022 00809 0100 4035 8 Emerson com Rosemount ...
Страница 16: ...Technical description Reference Manual May 2022 00809 0100 4035 16 Emerson com Rosemount ...
Страница 22: ...Operating modes Reference Manual May 2022 00809 0100 4035 22 Emerson com Rosemount ...
Страница 46: ...Operation Reference Manual May 2022 00809 0100 4035 46 Emerson com Rosemount ...
Страница 48: ...10 Do a functional check Maintenance Reference Manual May 2022 00809 0100 4035 48 Emerson com Rosemount ...
Страница 52: ...Troubleshooting Reference Manual May 2022 00809 0100 4035 52 Emerson com Rosemount ...
Страница 56: ...Ordering information Reference Manual May 2022 00809 0100 4035 56 Emerson com Rosemount ...
Страница 62: ...Specifications Reference Manual May 2022 00809 0100 4035 62 Emerson com Rosemount ...
Страница 70: ...Wiring configurations Reference Manual May 2022 00809 0100 4035 70 Emerson com Rosemount ...
Страница 74: ...Support Reference Manual May 2022 00809 0100 4035 74 Emerson com Rosemount ...