28
Reference Manual
00809-0100-4377, Rev CA
Troubleshooting
January 2018
Troubleshooting
Table 4-1. Troubleshooting guide.
Symptom
(1)
1.
The corrective actions should be done with consultation of your system integrator.
Cause
Recommended Actions
Device does not show up on
segment
Unknown
Recycle power to device
No power to device
1. Ensure the device is connected to the segment.
2. Check voltage at terminals. There should be 9–32
Vdc.
3. Check to ensure the device is drawing current. There
should be approximately 17 mA.
Segment problems
Electronics failing
1. Electronics board loose in housing.
2. Replace electronics.
Incompatible network settings
Change host network parameters.
Refer to host documentation for procedure.
Device does not stay on
segment
(2)
2.
Wiring and installation 31.25 kbit/s, voltage mode, wire medium application guide AG-140 available from the fieldbus Foundation.
Incorrect signal levels.
Refer to host documentation for
procedure.
1. Check for two terminators.
2. Excess cable length.
3. Bad Power supply or conditioner
Excess noise on segment.
Refer to host documentation for
procedure.
1. Check for incorrect grounding.
2. Check for correct shielded wire.
3. Tighten wire connections.
4. Check for corrosion or moisture on terminals.
5. Check for Bad power supply.
Electronics failing
1. Tighten electronics board.
2. Replace electronics.
Other
1. Check for water in the terminal housing.
Содержание Rosemount 752 FOUNDATION
Страница 2: ......
Страница 6: ...6 Reference Manual 00809 0100 4377 Rev CA Title Page January 2018 Title Page ...
Страница 8: ...2 Reference Manual 00809 0100 4377 Rev CA Introduction January 2018 Introduction ...
Страница 28: ...22 Reference Manual 00809 0100 4377 Rev CA Configuration January 2018 Configuration ...
Страница 38: ...Reference Data January 2018 Reference Manual 00809 0100 4377 Rev CA Specifications and Reference Data 32 ...
Страница 47: ......