21
Reference Manual
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
UNITS_TYPE_#
The UNITS_TYPE_# parameter is generally selected via a drop-down menu with three options: AUTO,
CUSTOM, or NONE. Select AUTO only when the parameter to be displayed is pressure, temperature, or
percent. For other parameters, select CUSTOM and be sure to configure the CUSTOM_UNITS_#
parameter. Select NONE if the parameter is to be displayed without associated units.
CUSTOM_UNITS_#
Specify custom units to be displayed with the parameter. Enter up to six characters. To display Custom
Units the UNITS_TYPE_# must be set to CUSTOM.
Figure 2-5. Configuring the LCD to Display Data from a Different Device on the Fieldbus Segment
PID
LCD
Configuration Block
TT102
71.2
DEG C
Characterizer
DISPLAY_PARAM_SEL = n n= 1 - 8
For each value displayed:
BLK_TAG_n
BLK_TYPE_n
PARAM_INDEX_n
CUSTOM_TAG_n
UNITS_TYPE_n
CUSTOM_UNITS_n
Arithmetic
Input Selector
TAG= ISEL 1300
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
OUT
Example: Display Value #1
BLK_TAG_1
= ISEL 1300
BLK_TYPE_1
= Input Selector
PARAM_INDEX_1
= IN_1
CUSTOM_TAG_1
= TT102
UNITS_TYPE_1
= CUSTOM
CUSTOM_UNITS_1 = DEG C
Linked from AI Block in
Temperature Transmtter TT102
IN_1
IN_2
IN_3
IN_4
IN_1
IN_2
Integrator
IN_1
IN_2
OUT
OUT
OUT
OUT_1
OUT_1
PV
SP
IN
CAS_IN
BKCAL_OUT
BKCAL_IN
RCAS_IN
ROUT_IN
RCAS_OUT
ROUT_OUT
TRK_VAL
FF_VAL
Содержание Rosemount 752 FOUNDATION
Страница 2: ......
Страница 6: ...6 Reference Manual 00809 0100 4377 Rev CA Title Page January 2018 Title Page ...
Страница 8: ...2 Reference Manual 00809 0100 4377 Rev CA Introduction January 2018 Introduction ...
Страница 28: ...22 Reference Manual 00809 0100 4377 Rev CA Configuration January 2018 Configuration ...
Страница 38: ...Reference Data January 2018 Reference Manual 00809 0100 4377 Rev CA Specifications and Reference Data 32 ...
Страница 47: ......