Table 6-1: Maintenance and Troubleshooting Suggestions
(continued)
Symptom
Corrective actions
Acoustics Failure
1. Reset the device.
2. If the condition persists, replace the device.
Waveguide Temperature
Failure
1. Reset the device.
2. If the condition persists, replace the device.
Radio Failure
1. Reset the device.
2. If the condition persists, replace the device.
Supply Voltage Failure
1. Replace the power module.
2. If the condition persists, replace the device.
Electronics Warning
1. Reset the device.
2. Reconfirm all configuration items in the device.
3. If the condition persists, replace the device.
Acoustics exceeded the
limits
1. Check process for possible saturation condition.
2. Reset the device.
3. If the condition persists, replace the device.
Electronics Temperature
exceeded the limits
1. Verify ambient temperature is within the transmitter’s range.
2. Reset the device.
3. If the condition persists, replace the device.
Waveguide Temperature
exceeded the limits
1. Verify process temperature is within the transmitter’s range.
2. Reset the device.
3. If the condition persists, replace the device.
Supply Voltage Low
1. Replace the power module.
Database Memory
Warning
1. Reset the device.
2. Reconfirm all configuration items in the device.
3. If logging dynamic data not needed, this advisory can be safely
ignored.
Simulation Active
1. Verify that simulation is no longer required.
2. Disable Simulation mode in Service Tools.
3. Reset the device.
Short Battery Life
1. Check that Power Always On mode is off.
2. Verify device is not installed in extreme temperatures.
3. Verify that device is not a network pinch point.