50
Reference Manual
00809-0100-4728, Rev MB
July 2016
Rail mount transmitter with threaded sensor
1. Attach the transmitter to a suitable rail or panel.
2. Attach the thermowell to the pipe or process container wall. Install and tighten the thermowell before
applying pressure.
3. Attach necessary extension nipples and adapters. Seal the nipple and adapter threads with thread
sealant.
4. Screw the sensor into the thermowell. Install drain seals if required for severe environments or to
satisfy code requirements.
5. Screw the connection head to the sensor.
6. Attach the sensor lead wires to the connection head terminals.
7. Attach additional sensor lead wires from the connection head to the transmitter.
8. Attach and tighten the connection head cover. Enclosure covers must be fully engaged to meet
explosion-proof requirements.
9. Set the transmitter failure mode switch.
10.Attach the sensor wires to the transmitter.
A. Rail mount transmitter
D. Threaded style sensor
B. Threaded sensor connection head
E. Threaded thermowell
C. Standard extension
A
D
E
C
B
Содержание Rosemount 644 HART
Страница 2: ......
Страница 16: ...6 Reference Manual 00809 0100 4728 Rev MB Introduction July 2016 Introduction ...
Страница 80: ...70 Reference Manual 00809 0100 4728 Rev MB Operation and Maintenance July 2016 Operation and Maintenance ...
Страница 86: ...76 Reference Manual 00809 0100 4728 Rev MB Troubleshooting July 2016 Troubleshooting ...
Страница 120: ...Product Certifications July 2016 Reference Manual 00809 0100 4728 Rev MB 110 Product Certifications Sheet 2 of 2 ...
Страница 122: ...Product Certifications July 2016 Reference Manual 00809 0100 4728 Rev MB 112 Product Certifications ...
Страница 138: ...128 Reference Manual 00809 0100 4728 Rev MB Index July 2016 Index ...
Страница 139: ......