22
Manual Supplement
00809-0300-4570, Rev BA
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
19. All of the parameters in DeltaV are now set. To send this configuration to the DeltaV controller,
I/O
under the expanded controller menu must be right-clicked. Select
Download -> I/O
to begin the
configuration download.
20. Right-click on
Added device
and select
Diagnose
to verify the communication status. Select a
dataset and double-click on
StrtRegAddr
to verify the values of the registers.
Table 1-4. Configuration for Two Datasets that Display a 3D Solids Scanner’s 13
Parameters
Parameter
Dataset 1
Dataset 2
DeltaV data type
16 bit unit w/Status
String w/Status
PLC data type
Holding registers
Holding registers
PLC register offset
0
24
Number of values
24
2