11
Reference Manual
00809-0100-4022, Rev GA
Configuration
September 2016
Configuration
Figure 2-2. Local Zero and Span Locations
Rerange with AMS Device Manger only
Right click on the device and select
Configuration Properties
from the menu. In the
Basic
Setup
tab, locate the
Analog Output
box and perform the following procedure:
1.
Enter the lower range value (LRV) and the upper range value (URV) in the fields
provided. Select
Apply
.
2.
An
Apply Parameter Modification
screen appears, enter desired information and
select
OK
.
3.
After carefully reading the warning provided, select
OK
.
Rerange with a pressure input source and AMS Device
Manger
Right click on the device, choose
Calibrate
, then
Apply values
from the menu.
1.
Select
Next
after the control loop is set to manual.
2.
From the
Apply Values
menu, follow the online instructions to configure lower and
upper range values.
3.
Select
Exit
to leave the
Apply Values
screen.
4.
Select
Next
to acknowledge the loop can be returned to automatic control.
5.
Select
Finish
to acknowledge the method is complete.
2.7.3
Damping
The Damp command introduces a delay in processing which increases the response time of
the transmitter; smoothing variations in output readings caused by rapid input changes.
Determine the appropriate damp setting based on the necessary response time, signal
stability, and other requirements of the of loop dynamics of your system. The default
damping value is 0.4 seconds and is user-selectable from 0.3 to 60 seconds.
A. Magnetic span target
B. Magnetic zero target
Fast Keys
1, 3, 6
B
A