Quick Installation Guide

00825-0100-4738, Rev BA
October 2009

Rosemount 3095FB

17

Содержание Rosemount 3095FB MultiVariable MODBUS

Страница 1: ...A October 2009 Rosemount 3095FB MODBUS Step 1 Mount the Transmitter Step 2 Consider Housing Rotation Step 3 Connect the Wiring and Power Up Step 4 Verify Configuration Step 5 Trim the Transmitter Product Certifications Rosemount 3095FB MultiVariable Transmitter with MODBUS Protocol ...

Страница 2: ...number 00809 0100 4738 It does not provide instructions for configuration diagnostics maintenance service or troubleshooting Refer to the appropriate reference manual for more instruction These manuals are also available electronically on www rosemount com WARNING Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be in accordance w...

Страница 3: ...ount beside or below the taps 3 Mount the transmitter so that the drain vent valves are oriented upward Gas Flow Applications 1 Place taps in the top or side of the line 2 Mount beside or above the taps Steam Flow Applications 1 Place taps to the side of the line 2 Mount beside or below the taps 3 Fill impulse lines with water Panel Mount 1 1 Panel bolts are customer supplied Pipe Mount Flow Flow ...

Страница 4: ...on set screw Field Installation 1 Mount the transmitter a Install the flange or flange adapter bolt finger tight b Torque bolts to initial torque value using a cross pattern see Table 1 When installing to a mounting bracket torque bolts to 125 in lb 169 N m 2 If security jumpers are not installed the transmitter will operate normally with the default security off Verify baud rate Default baud rate...

Страница 5: ... and follow the steps below Installing an Armored Shielded RTD Cable See Figure 3 a Fully engage the black cable connector to the 3095 RTD connector b Tighten the cable adapter until metal contacts metal c Install the compression fitting d Tighten the cap onto the compression fitting Figure 3 Armored Shielded RTD Cable Washer Cap Black Cable Connector RTD Cap Conductive Bushing Connect to RTD Comp...

Страница 6: ...g a ATEX IECEx Flameproof 3095 RTD Cable See Figure 5 a Fully engage the black cable connector to the 3095 RTD Connector b Tighten the cable adapter and cable gland until metal contacts metal Figure 5 ATEX IECEx Flameproof RTD Cable 5 Check all process connections for leaks 6 Connect the appropriate wiring see Step 5 Ground the transmitter according to national and local electrical codes Install f...

Страница 7: ...ment representative for more information Use the following bolt installation procedure 1 Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation However no additional lubricant should be applied when installing either type of bolt 2 Finger tighten the bolts 3 Torque the bolts to the initial torque value using a crossing pattern S...

Страница 8: ...nstallation to compensate for seating of the PTFE o ring Bolt Material Head Markings Initial Torque Final Torque Carbon Steel CS 300 in lbs 650 in lbs Stainless Steel SST 150 in lbs 300 in lbs Failure to install proper flange adapter O rings may cause process leaks which can result in death or serious injury The two flange adapters are distinguished by unique O ring grooves Only use the O ring tha...

Страница 9: ...2 or larger Runs from 1000 to 4000 feet 305 to 1219 m should be AWG 20 or larger Wiring should not exceed AWG 16 4 Plug and seal unused conduit connections 5 Install wiring with a drip loop Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing Figure 8 shows wiring connections necessary to power a 3095 and enable communications The 3095FB requires a ...

Страница 10: ...Interface Software Site License Part Number 03095 5106 0002 RS 485 Converter and Cable Verify Tag Information 1 Click Transmitter on the taskbar 2 Click Device Info from the drop down menu 3 Verify tag information 4 Click OK to exit Verify Damping 1 Click Transmitter on the taskbar 2 Click Damping from the drop down menu 3 Verify damping settings for DP SP and PT 4 Click OK to exit Verify Units of...

Страница 11: ... the offset trim point to trim DP Offset Zero 5 Click Trim to complete the sensor trim Trim SP Offset Zero AP GP 1 When performing a offset or zero SP trim ensure the low side block valve is closed the equalize valve is open and the high side block valve is closed Then open vent to atmosphere 2 Click Maintenance Sensor Trim on the taskbar 3 Click SP option 4 click Offset Trim option 5 If using GP ...

Страница 12: ...eering Practice Transmitter Attachments Process Flange Manifold Sound Engineering Practice Electro Magnetic Compatibility EMC 2004 108 EC 3095F Flow Transmitters EN 61326 1 1997 A1 A2 and A3 Ordinary Location Certification for Factory Mutual As standard the Rosemount 3095FB transmitter has been examined and tested to determine that the design meets basic electrical mechanical and fire protection r...

Страница 13: ...320X II 1 2 G Ex d IIC T5 50 C Tamb 80 C T6 50 C Tamb 65 C Vmax 55V dc 1180 Special Conditions for Safe Use x The device contains a thin wall diaphragm Installation maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions for installation and maintenance shall be followed in detail to assure safety during its ...

Страница 14: ...Quick Installation Guide 00825 0100 4738 Rev BA October 2009 Rosemount 3095FB 14 ...

Страница 15: ...Quick Installation Guide 00825 0100 4738 Rev BA October 2009 Rosemount 3095FB 15 ...

Страница 16: ...Quick Installation Guide 00825 0100 4738 Rev BA October 2009 Rosemount 3095FB 16 ...

Страница 17: ...Quick Installation Guide 00825 0100 4738 Rev BA October 2009 Rosemount 3095FB 17 ...

Страница 18: ...Quick Installation Guide 00825 0100 4738 Rev BA October 2009 Rosemount 3095FB 18 ...