4. Check for corrosion or moisture on terminals.
5. Check for bad power supply.
6. Check for electrically noisy equipment attached to the instrument ground.
Electronics failing
Recommended actions
1. Tighten electronics board.
2. Replace electronics.
Other
Recommended action
Check for water in the terminal housing.
6.6
Troubleshooting and diagnostic messages
Detailed descriptions of the possible messages that will appear on either the LCD display, a
Handheld Communicator, or a PC-based configuration and maintenance system are listed
in the sections below. Use the sections below to diagnose particular status messages.
6.6.1
Incompatible module
NE107 and Plantweb
™
alert: Failure
The pressure sensor is incompatible with the attached electronics.
Recommended actions
•
Replace electronics board or sensor module with compatible hardware.
Default configuration
Enabled
LCD display message
^^^^XMTR MSMTCH
Associated status bits
0x10000000
6.6.2
Sensor failure
NE107 and Plantweb
™
alert: Failure
An error has been detected in the pressure sensor.
Recommended actions
•
Check the interface cable between the sensor module and the electronics board.
•
Replace the sensor module.
Reference Manual
Troubleshooting
00809-0100-4774
July 2020
Reference Manual
111
Содержание Rosemount 3051 CF Series
Страница 4: ...4 ...
Страница 56: ...Configuration Reference Manual July 2020 00809 0100 4774 56 Rosemount 3051 ...
Страница 92: ...Electrical installation Reference Manual July 2020 00809 0100 4774 92 Rosemount 3051 ...
Страница 102: ...Operation and maintenance Reference Manual July 2020 00809 0100 4774 102 Rosemount 3051 ...
Страница 118: ...Troubleshooting Reference Manual July 2020 00809 0100 4774 118 Rosemount 3051 ...
Страница 138: ...Reference data Reference Manual July 2020 00809 0100 4774 138 Rosemount 3051 ...
Страница 145: ...Reference Manual 00809 0100 4774 July 2020 Reference Manual 145 ...