Figure 5-3: Typical Settings for Low Level Applications
Dry On
Wet On
Seconds Delay
0.3
0.3
30
10
3
30
10
1
3
1
A
A. Mode “Wet On” and 1 second time delay
5.1.1
Set the mode switch and switching time delay
Procedure
1. Select “Dry on” or “Wet on” mode.
2. Select 0.3, 1, 3, 10, or 30 seconds for the delay before switching output state.
Note
There is a five second delay before changes to the mode and time delay become
active.
5.2
LED indication status
shows the different operation statuses and how they are indicated by the LED.
Table 5-1: LED Indications
LED flash rate
Switch status
Continuous
Output state is on.
1 every second
Output state is off.
1 every 2 seconds
Uncalibrated.
1 every 4 seconds
Load fault; load current too high; load short
circuit.
2 times / second
Indication of successful calibration.
3 times / second
Internal PCB fault.
Off
Problem (e.g. supply).
Operation
Reference Manual
March 2022
00809-0100-4030
54