and
•
for parameter configuration
5.2 Configuration tools
5.2.1 Local operator interface (LOI)
When ordered, the LOI can be used for commissioning the device. To activate
the LOI, push either configuration button located under the top tag of the
transmitter. See
for operation and menu
information. The security jumper prevents changes made using the LOI.
Note
Buttons must be fully engaged ≈ 0.5-in. (10 mm) of travel.
Table 5-1: LOI Button Operation
Button
Action Navigation
Character Entry
Save?
Scroll
Moves down menu
categories
Changes character
value
Changes between
Save and Cancel
Enter
Selects menu
category
Enters character and
advances
Saves
(1)
Characters blink when they can be changed.
Figure 5-1: LOI Menu
1. ADDRESS
6. IDENTIFICATION #
7. EXIT
4. DAMPING
5. DISPLAY
3. UNITS
2. CALIBRATION
PRESSURE
FLOW
LEVEL
TEMPERATURE
0-126
ZERO
LOWER SENSOR
UPPER SENSOR
RESET FACTORY
5.3 Class 2 Master
The Rosemount 2051 PROFIBUS DD and DTM files are available at
or by contacting your local salesperson.
for steps to configure the transmitter for Pressure
measurement. See Rosemount 2051
for Flow or Level
configuration instructions.
Table 5-2: Pressure Configuration via Class 2 Master
Steps
Actions
Set blocks to Out of Service
Put Transducer Block into Out of Service mode
February 2019
Quick Start Guide
Quick Start Guide
17