54 • RLDS I&O Manual
026-1309 Rev 8
LOOP FAULT - Open current loop
PRESSURE RANGE - Pressure out of range
BENCH TEMP - Bench temperature out of range
BOX TEMP - Box temperature fault
11.4.3. RLDS Configuration Option
(CONFIG OPTION) Screen
From the Operation Select (OPTION) screen, (
RLDS CONFIG
by pressing the
right arrow key, selecting
3
, and pressing the down ar-
row key twice. The CONFIG OPTION screen dis-
plays and allows the user to configure the selected
RLDS:
Press the right arrow key to enable you to change the
number selection that appears next to
CONFIG OP-
TION
. When a right arrow appears after
CONFIG OPTION
, press the number key of the
desired screen (1,2, or 3). Press the down arrow key
twice to display the selected screen.
• Select 1 to access the General Configuration 1
Screen
See
Section 11.4.4., General Configuration 1
• Select 2 to access the Time/Date screen
See
Section 11.4.8., Time/Date Screen
.
• Select 3 to access the Calibrate/Refrigerant
screens
See
Section 11.4.9., Calibrate Gas Screen 1
11.4.4. General Configuration 1
Screen
From the CONFIG OPTION screen, press the right
arrow key and then press the
1
key for
RLDS CTRL
.
Press the down arrow key twice to display the General
Configuration 1 (a non-editable) screen:
Press the down arrow key to display the General Con-
figuration 2 screen:
11.4.5. General Configuration 2
Screen
Press the right arrow key to activate the
U1
field so
you can change the name of the controller. Use the
right and left arrow keys to move across the field to
select each letter, and remember to use the “.” and
“
—
” keys to toggle letters.
Press the down arrow key to move from the
U1
field
to the
BUZZER
field. The default for this field is set
to
NONE.
Use the “.” and “
—
” keys to scroll through
the choices:
NONE
,
ALARM
,
FAULT
,
LEAK
,
SPILL
,
EVAC
, or
MN OFF
(monitor is
offline and is no longer monitoring the refrigerant
lines).
Press the down arrow key to move from the
BUZZER
field to the
AL ACK
field. The default for this field is
set to
MANUAL
, but it is recommended the setting
be changed to
AUTO
so the zone can
automatically reset itself after the condition clears.
CONFIG OPTION: 1
1 = RLDS CTRL
2 = TIME/DATE
3 = CALIB GASES
Ux: ENABLED:DISABLED
Ux- ZONES: 8
Ux- MODEL: 300
Ux- REV : 1.12
NOTE: x is the RLDS currently being
accessed.
U1: NAME OF CONTROLLER
1 - BUZZER: NONE
1 - AL ACK: MANUAL
NOTE: The “blank” line is used to provide a
cursor so the user knows which character they
are editing. The “.” and “—” keys are used to
scroll an individual character selection or
numeric numbers can be entered directly.