40 • RLDS I&O Manual
PPM by placing the cursor on the spikes cause by the
sample. If the bag was large enough for multiple
samples, average the most stable ones.
The new CAL factor is computed by dividing the
known gas value by the measured value. Typically
this value will be between 0.95 and 1.05. This value is
stored in non-volatile memory.
8.9.6. Programming New Gases
As new refrigerants come into use, the RLDS
allows the addition of these new gases to its on-board
refrigerant gas library. At the end of the gas library list
is an option labeled
CUSTOM
for adding new gases.
From the
Calibration screen
use the left/right arrows
to select
CUSTOM
from the list of refrigerants. Next,
press
ENTER
, and use the up/down arrow keys to
enter the calibration factor.
The selection of the matching gas and
CAL
factor is
performed by analyzing the new refrigerant. Once the
matching gas is determined, field calibration is
possible by using the same procedure as for other
refrigerants. When the new gas entry is complete,
simply set up the appropriate zone for
CUSTOM
.
Program the instrument for a new gas as follows:
1. From the
Calibration screen
, use the
PREV
GAS
or
NEXT GAS
options to scroll through
the list of available choices until the
CUSTOM
option is displayed.
2. Select the
CUSTOM
option. Press
ENTER
to
accept the new entry or
ESC
to revert to the
previous setting.
3. Enter the new CAL Factor as received from
Emerson Electronics and Solutions.
Figure 8-11
- Custom Gas Screen