Configuring an Embedded RSTi-EP PROFINET
Controller
CPE100 support configuring LAN2 as an embedded PROFINET Controller. Instead of
Configuring a PNC001 into a rack/slot location (
Figure 32), LAN2 in the target is configured as a PROFINET Controller (Figure 34).
Figure 34: CPE100/CPE115 Embedded PROFINET Controller Configured on LAN2
3.4
Configuring PROFINET System Redundancy
To enable PROFINET System Redundancy in a CPL410/CPE400 project, select the
CPL410/CPE400 target in the PAC Machine Edition Navigator and use the Property Inspector
to change the Enable Redundancy target property to True.
To enable PROFINET System Redundancy in a CPE330 project, select the CPE330 target in
the PAC Machine Edition Navigator and use the Property Inspector to change the Enable
Redundancy target property to True. The Dual HWC property then defaults to True and
must remain True.
To enable PROFINET System Redundancy for a PNC001, select the CPE330 or CRU320 target
in the PAC Machine Edition Navigator and use the Property Inspector to change the Enable
Redundancy target property to True. The Dual HWC property then defaults to True and
must remain True.
Содержание PACSystems RX3i
Страница 1: ...USER MANUAL GFK 2571R May 2021 PACSystemsTM RX3i and RSTi EP PROFINET I O CONTROLLER USER MANUAL ...
Страница 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Страница 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Страница 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Страница 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...