I N S T R U C T I O N M A N U A L R E V 4 . 2
55
SECTON 11 ALARM MATRIX
High mg
Alarm 011:
0=open, 1=
closed
High Op AL
012: 0=open,
1= closed
mg/Op Alarm
silence O13:
0= open, 1=
closed
E.W. Op AL
O15: 0=
open, 1=
closed
E.W. mg
Alarm O16:
0= open, 1=
closed
Auto alarm reset without pushing rest button.
Start 0%, use test value above High set points.
0
0
0
0
0
> Hi Mg 150mg set point after delay satisfied (AL)
1
1
1
1
1
> Hi Op 20% set point after delay satisfied (AL)
1
1
1
1
1
Return to 0%
0
0
0
0
0
Auto alarm reset pushing rest button before returning to zero.
Start 0%, use test value above High set points.
0
0
0
0
0
> set point after delays satisfied (AL)
1
1
1
1
1
> set point EW, Reset button pushed
1
1
1
1
1
> set point Process Alarm, Reset button pushed
1
1
0
1
1
Return to 0%
0
0
0
0
0
Manual alarm reset after returning to zero.
Start 0%, use test value above High set points.
0
0
0
0
0
> set point after delays satisfied (AL)
1
1
1
1
1
Return to 0%
1
1
1
1
1
Process Alarm reset button pushed
0
0
0
1
1
EW reset button pushed
0
0
0
0
0
Manual alarm reset before, than after returning to zero.
Start 0%, use test value above High set points.
0
0
0
0
0
> set point after delay satisfied (AL)
1
1
1
1
1
Process Alarm reset button pushed
1
1
0
1
1
EW reset button pushed
1
1
0
1
1
Return to 0%
1
1
0
1
1
Process Alarm reset button pushed
0
0
0
1
1
EW reset button pushed
0
0
0
0
0
Содержание OPM4001
Страница 31: ...I N S T R U C T I O N M A N U A L R E V 4 2 30 ABOUT PAGE About page displays the basic setup information ...
Страница 36: ...I N S T R U C T I O N M A N U A L R E V 4 2 35 ANALOG OUTPUT CONNECTIONS ...
Страница 52: ...I N S T R U C T I O N M A N U A L R E V 4 2 51 OPM6127 1OF3 CONTROL UNIT TO SENSOR WIRING DUAL BLOWER ...
Страница 53: ...I N S T R U C T I O N M A N U A L R E V 4 2 52 OPM6127 2OF3 CONTROL UNIT TO SENSOR WIRING SINGLE BLOWER ...
Страница 54: ...I N S T R U C T I O N M A N U A L R E V 4 2 53 OPM6127 3OF3 CONTROL UNIT TO SENSOR WIRING NO BLOWER ...