RSTi-OM User Manual
Section 8
GFK-3212A
Jun 2021
Utilizing IOLM Features
82
In addition, the IO-Link Diagnostics page displays the following information:
Figure 69: IO-Link Diagnostics
8.4
Data Validation
You can use this procedure to configure data validation.
Although you can make configuration changes using the web page, PROFINET IO configuration
parameters overwrite the values on the
IO-Link Settings
page. See
IO-Link Port Settings (IO-Link Port
for PROFINET IO configuration procedures.
1.
Click Configuration | IO-Link Settings.
2.
Click the EDIT button on the port you want to configure for data validation.
3.
Select Loose or Strict to enable data validation.
•
Loose - the slave device's PDI/PDO lengths must be less than or equal to the user-
configured values.
•
Strict - the slave device's PDI/PDO lengths must be the same as the user-configured
values.
4.
Click the GET ATTACHED button or manually enter the PDI and PDO length.
Figure 70: Data Validation: Strict
5.
Click the SAVE button.
6.
If data validation fails, the IO-Link port LED flashes red and the IO-Link Diagnostics page
displays an error.