Reference Manual
Specifications
MAN-0091, Revision 8
June 2016
Specifications
19
Section 7:
Specifications
7.1
Electrical
7.1.1
Voltage range
10.5 to 32 Vdc
7.2
Performance
7.2.1
Response time
T50 ≤ 4.3 seconds
T60 ≤ 7.0 seconds
T90 ≤ 11.0 seconds
* Methane at room temperature
7.2.2
Accuracy
± 5 % LEL or 10 % of applied, whichever is greater
* Methane at room temperature
7.2.3
Zero Drift
< 5 % full scale per year
7.2.4
Repeatability
± 2 % LEL full scale
7.2.5
Detection Range
0-100 % LEL
7.2.6
Calibration Frequency
Twelve (12) months
7.2.7
Storage temperature
-40°C to +70°C (-40°F to +158°F)
7.2.8
Operating temperature
-40°C to +75°C (-40°F to +167°F)