20 • MRLDS-450 Refrigerant Gas Detection I&O Manual
026-1316 Rev 0
4.2.3.2. Change Unlock Code
To prevent unauthorized access to instrument configuration and calibration, the
default instrument unlock code should be changed during commissioning. To
change unlock code:
• On the
Configure
tab select
Modbus Unlock Code
. Enter the new 4-digit unlock
code for instrument and select
OK
.
• The instrument must be restarted for changes to take effect. Selecting the
Home
tab,
then
Restart
will reboot the device.
• Reconnect to instrument to confirm the unlock code has been updated.
IMPORTANT: If the custom unlock code is forgotten, the unlock code may be reset to
default value (1234) by resetting system to factory defaults. Refer to Section 4.1.6., Reset
System to Factory Default Settings for the system reset procedure. Note that a system reset
will return all custom system configurations to defaults.
4.2.3.3. Change Bluetooth
®
Passcode
To prevent unauthorized access to instrument status, the default instrument
Bluetooth® passcode code should be changed during commissioning. To change
Bluetooth® passcode:
• On the
Configure
tab select
Bluetooth Passcode
. Enter new 6-digit passcode for the
instrument and select
OK
.
• The instrument must be restarted for changes to take effect. Selecting the
Home
tab,
then
Restart
will reboot the device.
• Reconnect to instrument to confirm the Bluetooth
®
Passcode has been updated.
IMPORTANT: If the custom passcode is forgotten, the unlock code may be reset to default
value (123456) by resetting system to factory defaults. Refer to Section 4.1.6., Reset System
to Factory Default Settings for system reset procedure. Note that a system reset will return
all custom system configurations to defaults.