Mentor MP User Guide
www.controltechniques.com Issue: 3
3. Either:
•
Press the red
reset button
•
Toggle the reset digital input, or
•
Carry out a drive reset through serial communications by
setting Pr
10.38
to 100 (ensure that Pr.
xx.00
returns to 0).
5.10 Differences between European and
USA defaults
5.11 Displaying parameters with non-
default values only
Select dIS.dEf in Pr
xx.00
, the only parameters that will be visible to the
user will be those containing a non-default value. This function does not
require a drive reset to become active. To deactivate this function, return
to Pr
xx.00
and enter a value of 0.
Please note that this function can be affected by the access level
enabled. You must refer to section 5.13
for more information regarding access level.
5.12 Displaying destination parameters
only
Select dIS.dESt in Pr
xx.00
, the only parameters that will be visible to
the user will be destination parameters. This function does not require a
drive reset to become active. To deactivate this function, return to
Pr
xx.00
and enter a value of 0.
Please note that this function can be affected by the access level
enabled You must refer to section 5.13
for further information regarding access levels.
5.13 Parameter access level and security
The parameter access levels determine whether the user has access to
Menu 0 (in sub block mode) only or to all of the advanced menus (Menus
1 to 23), in addition to Menu 0 (in linear mode).
The user security determines whether the access to the user is read only
or read write.
The user security and the parameter access level can operate
independently of each other as shown in Table 5-5 .
Table 5-5 User security and parameter access levels
RW = Read / write access RO = Read only access
The default settings of the drive are parameter access level L1 and User
Security Open, i.e. read / write access to Menu 0 with the advanced
menus, not visible
5.13.1 User security
The user security, when set, prevents write access to any of the
parameters (other than Pr
11.44
(
SE14, 0.35
) Access Level) in any menu.
Figure 5-8 User security open
5.13.2 Setting user security
Enter a value between 1 and 999 in Pr
11.30
and press the
button;
the security code has now been set to this value. To activate the security,
the access level must be set to Loc in Pr
11.44
(
SE14, 0.35
). When the
drive is reset, the security code will have been activated and the drive
returns to access level L1. The value of Pr
11.30
will return to 0 in order
to hide the security code. At this point, the only parameter that can be
changed by the user is the access level Pr
11.44
(
SE14, 0.35
).
5.13.3 Unlocking user security
Select a read write parameter to be edited and press the
button; the
upper display will now show CodE.
Use the arrow buttons to set the security code and press the
button.
With the correct security code entered, the display will revert to the
parameter selected in edit mode. If an incorrect security code is entered
the display will revert to parameter view mode.
To lock the user security again, set Pr
11.44
(
SE14, 0.35
) to Loc and
press the
reset button.
Pr
Description
Default
2.06
S ramp enable
Eur: OFF (0), USA: On (1)
3.51
Tachometer voltage rating
(Fb02, 0.72)
Eur: 60.00, USA: 50.00
5.09
,
21.09
Armature rated voltage
(SE06, 0.27)
480V drive Eur: 440, USA:500
5.28
Field weakening
compensation disable
Eur: OFF (0), USA On (1)
5.59
,
21.08
Back emf set point
480V drive Eur: 440, USA:500
5.65
Economy timeout
Eur: OFF (0), USA: On (1)
5.70
,
21.24
Rated field current
(SE10, 0.31)
Size 1: Eur: 2.00, USA: 8.00
Size 2A & B Eur: 3.00, USA:
20.00 Size 2C & D Eur: 5.00,
USA 20.00
5.73
,
21.23
Rated field voltage
(SE11, 0.32)
Eur: 360, USA: 300
5.75
Field voltage mode
Eur: OFF (0), USA: On (1)
7.15
Analog input 3 mode
(in01, 0.81)
Eur: th (8), USA: VOLt (6)
Parameter
access level
User security
Menu 0 status
Advanced
menus status
L1
Open
Sub block RW
Not visible
L1
Closed
Sub block RO
Not visible
L2
Open
Linear RW
RW
L2
Closed
Linear RO
RO
Pr 0.00
Pr 0.01
Pr 0.02
Pr 0.03
Pr 0.90
Pr 1.00
Pr 1.01
Pr 1.02
Pr 1.03
Pr 1.50
Pr 1.51
............
............
............
............
............
............
............
............
Pr 0.00
Pr 0.01
Pr 0.02
Pr 0.03
Pr 0.89
Pr 0.90
Pr 1.00
Pr 1.01
Pr 1.02
Pr 1.03
Pr 1.50
Pr 1.51
Pr 23.00
Pr 23.01
Pr 23.02
Pr 23.03
Pr 23.10
Pr 23.11
............
............
............
............
............
............
............
............
User security open
- All parameters: Read / Write access
User security closed
- All parameters: Read Only access
(except Pr
(
)
11.44 SE14, 0.35
Pr 23.00
Pr 23.01
Pr 23.02
Pr 23.03
Pr 23.10
Pr 23.11
Pr 0.49
Pr 22.00
Pr 22.01
Pr 22.02
Pr 22.03
Pr 22.39
Pr 22.40
Pr 22.00
Pr 22.01
Pr 22.02
Pr 22.03
Pr 22.39
Pr 22.40