50
Reference Manual
24625020, Rev AA
March 2017
tightening torque used must be the minimum to achieve this. Failure to comply
with this limitation may cause damage to the port or to the electrode from over
tightening.
13.
Re-connect conductors (leads) to the electrode.
14.
Repeat steps
for any other electrode in need of repair or replacement.
15.
Replace the electrode cover and secure.
16.
If applicable, tighten the electrode cable glands.
This completes the procedure.
5.4
Periodic system overhaul
During a system overhaul, the Hydratect 2462 system must be protected against
mechanical damage. Protect it using any rigid material, such as packing cases, that prevents
impact damage.
When the system overhaul is complete, remove the protective material and use the periodic
check procedure (on
) to verify the correct operation of the Hydratect 2462 system.
5.5
Electrode replacement parts
The electrode replacement parts listed here should be readily available, on site, whenever a
periodic check takes place or electrode repairs are made.
Spare electrodes
(see
Section 2: Installing the electrodes
for part numbers)
Spare electrode cables
(see
Содержание Mobrey Hydratect 2462
Страница 1: ...Reference Manual 24625020 Rev AA March 2017 Mobrey Hydratect 2462 Steam Water Detection System ...
Страница 2: ......
Страница 16: ...10 Reference Manual 24625020 Rev AA Introduction March 2017 Introduction ...
Страница 26: ...20 Reference Manual 24625020 Rev AA Installing the electrodes March 2017 Installing the electrodes ...
Страница 52: ...46 Reference Manual 24625020 Rev AA System Testing March 2017 System Testing ...
Страница 62: ...56 Reference Manual 24625020 Rev AA Electronics Servicing March 2017 Electronics Servicing ...
Страница 65: ......