Piping
Liebert
®
SRC
™
User Manual
44
Figure 5-7 Coiled expansion loops and offsets
5.2.7
Pipe Bends
When bending soft copper, use long-radius bends. Refer to
for minimum radius specifications.
5.2.8
In-line Refrigeration Components
Liebert SRC systems are provided with redundant systems that assure oil is properly returned to the
compressor. Sight glasses and solenoid valves may cause vapor to form in the liquid stream.
Table 5-8
Radii of coiled expansion loops and developed lengths of expansion offsets
Anticipated Linear
Expansion (LE)
(in.)
Nominal Tube Size (OD) in.
1/4
3/8
1/2
3/4
1/2
R
1
6
7
8
9
L
2
38
44
50
59
1
R
1
9
10
11
13
L
2
54
63
70
83
1-1/2
R
1
11
12
14
16
L
2
66
77
86
101
2
R
1
12
14
16
19
L
2
77
89
99
117
2-1/2
R
1
14
16
18
21
L
2
86
99
111
131
3
R
1
15
17
19
23
L
2
94
109
122
143
3-1/2
R
1
16
19
21
25
L
2
102
117
131
155
4
R
1
17
20
22
26
L
2
109
126
140
166
NOTE
Components such as oil traps, solenoid valves, filter-dryers, sight glasses, tee
fittings, and other after-market accessories are not permitted on the
refrigerant-piping system between the outdoor unit and the indoor unit.
NOTE
Over time, dryers may deteriorate and introduce debris into the system. The
designer and installer should verify that the refrigerant-piping system is free of
traps, sagging pipes, sight glasses, filter dryers, etc.
Large Tubing U-bend (>3/4 in.)
Loop
Small Tubing U-bend (<3/4 in.)
R
L
R
L
L
Содержание Liebert SRC Series
Страница 1: ...Liebert SRC User Manual Mini Split Cooling System ...
Страница 2: ......
Страница 18: ...Safety Symbols Liebert SRC User Manual 8 Page intentionally left blank ...
Страница 20: ...Model Number and Nomenclature Liebert SRC User Manual 10 Page intentionally left blank ...
Страница 28: ...Product Introduction Liebert SRC User Manual 18 Page intentionally left blank ...
Страница 122: ...Troubleshooting Liebert SRC User Manual 112 Page intentionally left blank ...
Страница 123: ......