Installation
23
Table 18
Electrical data—Quiet-Line models (95°F/35°C) 60Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
208/230-1
208/230-3
460-3
575-3
27
2
FLA
13.0
—
—
—
WSA
16.0
—
—
—
OPD
25
—
—
—
37
3
FLA
18.8
12.3
6.4
5.2
WSA
23.3
15.2
7.8
6.4
OPD
40
25
15
15
42
3.5
FLA
—
14.8
6.9
5.9
WSA
—
18.3
8.5
7.3
OPD
—
30
15
15
67
5
FLA
—
21.1
10.9
8.8
WSA
—
25.9
13.4
10.8
OPD
—
45
20
15
*
FLA
= Full Load Amps
WSA
= Wire Size Amps (minimum supply circuit current capacity)
OPD
= Overcurrent Protection Device (fuse or circuit breaker)
Model # 14, 20
and
96
are not available in Quiet-Line versions.
Table 19
Electrical data—Standard sound and ambient models (95°F/35°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1
200/230-3
380/415-3
13
1
FLA
9.9
—
—
19
1.5
FLA
10.9
—
—
26
2
FLA
12.7
—
4.9
36
3
FLA
18.4
—
7.0
41
3.5
FLA
—
15.3
8.5
66
5
FLA
—
24.1
13.2
95
8
FLA
—
—
20.3
*
FLA
= Full Load Amps
Table 20
Electrical data—High ambient models (105°F/41°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1
200/230-3
380/415-3
13
1
FLA
—
—
—
19
1.5
FLA
—
—
—
26
2
FLA
14.8
—
6.0
36
3
FLA
20.5
—
13.1
41
3.5
FLA
—
19.8
9.6
66
5
FLA
—
24.2
13.2
95
8
FLA
—
—
—
*
FLA