Installation
20
2.5.6 General System Charge Requirements
Liebert split system units are designed with quick-connect fittings and are factory-charged to proper
levels. Due to the wide range of operating ambients and sensitivity of the system components to
charge level, the system charge must be maintained at recommended levels.
If there is any doubt that the system has the correct refrigerant charge level, the correct
procedure is to remove the entire system charge, evacuate the system and weigh in the
recommended factory charge total for both units and any line sets or field piping.
Tables 7
,
8
,
11
and
12
are included for field piping allowances, condensing unit charges, line sets and
evaporator charges.
Total refrigerant charge = evap lines + condensing unit
NOTE
All condensing units and most evaporator units are fully charged with refrigerant. Some
evaporator units are shipped from the factory with a nitrogen holding charge only. (Refer to
evaporator serial tags.) If field-supplied refrigerant piping is installed, refrigerant must be
added to the system. Refer to
Figure 12
for field-supplied piping guidelines.
Table 12
Evaporator Charge Levels
Indoor Unit
Evaporator
Models
Charge R-407C
oz (kg)
Liebert
Mini-Mate2
MMD11/12E
3 (0.085)
MMD17/18E
4 (0.113)
MMD23/24E
7 (0.198)
MMD35/36E
7 (0.198)
MMD59/60E
4 (0.113)
MMD95/96E
7 (0.198) each circuit
Liebert DataMate
DME020E
4 (0.113)
DME027E
5 (0.141)
DME037E
6.5 (0.184)
Liebert Challenger
3000
BF/BU036E
9 (0.255)
BF/BU060E*
13 (0.368)
* Evaporator is charged with nitrogen at the factory