Liebert NXL UPS
Operation and Maintenance Manual
250-300-400-800kVA
Page 22
2.2.6.3
2.2.6.3
2.2.6.3
2.2.6.3
Adjustable Setpoints
These warning and alarm settings can be changed from the touchscreen. Press the box to
the left of each parameter to bring a popup window that will allow the parameter to be
changed.
Max Load Alarm
• Phase A (%)—10% to 105% (default: 100%)
• Phase B (%)—10% to 105% (default: 100%)
• Phase C (%)—10% to 105% (default: 100%)
• Delay (second)—0 to 60 (default: 5 seconds)
Manual Xfer Bypass Voltage Limits
• Manual Xfer Bypass Voltage Low Limit (%)—1% to
20% (default: 10%)
• Manual Xfer Bypass Voltage High Limit (%)—1% to 15% (default: 10%)
Figure 12 Adjustable setpoints parameters
Inlet Air Temp Warning
• Inlet Air Temp Warning—30°C to 40°C (default: 35°C)
NOTE
Temperature will display in both Celsius and Fahrenheit.