Liebert NXL UPS
Operation and Maintenance Manual
250-300-400-800kVA
Page
13
1.3 Options
A number of options are available from Liebert for your UPS system. (Some
options are not available for all ratings.) Described below are the most
frequently provided options. The first three battery items are required to
complete the UPS system. The remaining options provide improved system
performance or convenience. Other options are available. Contact your Liebert
sales representative for more information.
•
Battery and Racks
—The batteries provide power in the event of a power outage.
The Liebert NXL UPS can use a variety of battery types, provided the battery plant
is designed for the UPS DC voltage range and the load requirements of your
application. This option is required to complete the UPS system.
•
Battery Cabinets
—Valve-regulated, lead-acid (VRLA) sealed batteries are
available in matching cabinets for convenient installation and maintenance in
otherwise unprotected space.
Depending on the UPS module rating, two or more cabinets may be connected in
parallel to provide the additional run time. This option is required to complete the
UPS system.
•
Battery Breaker Disconnect
—The UPS system utilizes a separate optional
switch for remotely located batteries. A sensing circuit in the UPS module, set at
the battery low voltage limit, trips the BCB to safeguard the battery from excessive
discharge. The BCB has an undervoltage release mechanism designed to ensure
that during any shutdown or failure mode all battery potential is removed from the
UPS system. This option is required to complete the UPS system.
•
Input Current Distortion Filter
—This filter reduces input current reflected
harmonic distortion THD at full load. The filter is factory-installed in the UPS. This
filter also improves the input power factor at full load.
• External Maintenance Breaker
—This switchboard provides make-before-break
maintenance bypass. It includes: Maintenance Bypass Breaker (MBB),
Maintenance Isolation Breaker (MIB) and two Output Breakers (MOB).
•
Load Bus Synchronization
—The Load Bus Sync (LBS) option keeps two
independent UPS systems (and therefore their critical load buses) in sync, even
when the modules are operating on batteries or asynchronous AC sources. This
means that critical loads connected to both load buses can switch seamlessly
between the two.
•
Customer Alarm Interface
—This optional interface board allows the input and
display of eight alarms from customer-supplied contacts, each with a customer-
selected name of up to 19 characters.
The following attributes can be programmed for each alarm: latching, audible,
event log and time delay (0 to 99.9 seconds).
•
Temperature-Compensated Charging
—When the battery temperature exceeds
a preset limit (typically 25°C), this optional circuit proportionally reduces float
charging voltage to prevent overcharging the battery.
•
Battery Load Testing
—When activated, this option forces the battery string to
assume the load for a short period of time. The UPS then compares the test results
to data collected during the UPS commissioning to see if the battery system appears
to meet specifications.
The Liebert NXL will display status events for Battery Equalize, Battery Self-Test and
Battery Commissioning when those options are active.