Chapter 8 Options 49
Liebert
®
ITA 5kVA And 6kVA UPS User Manual
Table 8-17 Battery module options
Model Name
Description
U16-07C1
Battery module (2U)
Built-in 16-cell 12V 7.2A batteries, used to prolong the system running time.
Note: It is recommended to extend four battery modules, at least two. The
accessory of the battery module is a cable, used to connect the extended battery
module
Note
1. The battery loop and the AC input are not insulated, therefore hazardous voltage may exist between the battery port and the
earth. Never touch them by hand to avoid electrical shock.
2. Refer to
2.5.2 Connecting Battery Cables
for the method to connect the battery module. If the longer cables are needed, please
consult the dealers.
3. The maximal allowable charge current of the standard battery module is 2.16A, the maximal allowable charge current of the
standard UPS is 4A, and the maximal allowable charge current of the 10A charger is 10A, therefore the number of the standard
battery modules should be based on the charge capacity when you build the system.
8.2.2 Appearance Of Battery Module
Adjust the direction of the plastic panel on the battery module according to actual requirement. The appearance of the
battery module is shown in Figure 8-1.
Figure 8-55 Appearance of the battery module
There is no display panel on the front panel of the battery module. The plastic panel can be removed, as shown in
Figure 8-2.
Plastic panel
Figure 8-56 Removing the plastic panel
The battery module provides battery ports, battery fuse box and ventilation holes on the rear panel, as shown in Figure
8-3.