Introduction

1

1.0

I

NTRODUCTION

The Liebert IntelliSlot Relay Card (IS-RELAY) provides contact 

closure for remote monitoring of alarm conditions in your Liebert unit. 

The card is easy to install and integrates with other relay contact 

monitoring systems. 
This advanced power-management device is designed to function in 

units with a Liebert IntelliSlot port. Some examples are:

• Liebert Nfinity

• Liebert NX

• Liebert UPStation GXT3

Visit the Liebert Web site at 

www.liebert.com

 for the current list of 

supported products.
On supported units, the inverter shut-off command can be controlled 

from the computer directly connected to the UPS (via the factory-

installed DB9 connector) and will conserve battery power after the 

workstation shutdown is completed.
The Liebert IntelliSlot Relay Card is rated for 24VAC/VDC at 1A.

Inspecting Shipment on Receipt

Upon accepting shipment, inspect the packaging and product for any 

damaged or missing parts. If any damage is observed, report it to the 

shipping company and your local Emerson Network Power 

representative. If any components are missing, contact your local 

representative for replacement.
Items included with the shipment are:

• Liebert IntelliSlot Relay Card protected by an anti-static bag
• User manual

Содержание Liebert IntelliSlot IS-RELAY

Страница 1: ...ntelliSlot Relay Card User Manual Проконсультироваться и купить данное оборудование вы можете в компании АНД Системс адрес 125480 г Москва ул Туристская д 33 1 site https andpro ru тел 7 495 545 4870 email info andpro ru При обращении используйте промокод AND PDF и получите скидку ...

Страница 2: ...t 1 2 0 INSTALLATION 2 Required Parts and Tools 2 Instructions 2 3 0 PIN CONFIGURATION 4 4 0 JUMPER SETUP 5 Figures Figure 1 Pin location and numbering 4 Figure 2 Jumper location and numbering 5 Tables Table 1 Relay card pin configuration 4 Table 2 Jumper connections 5 ...

Страница 3: ...upported units the inverter shut off command can be controlled from the computer directly connected to the UPS via the factory installed DB9 connector and will conserve battery power after the workstation shutdown is completed The Liebert IntelliSlot Relay Card is rated for 24VAC VDC at 1A Inspecting Shipment on Receipt Upon accepting shipment inspect the packaging and product for any damaged or m...

Страница 4: ...ort location and orientation 3 Remove the two retaining screws from the Liebert IntelliSlot port cover plate on the unit Save the screws for reassembly in Step 5 4 As you insert the card make sure the holes are aligned with those on the UPS Initially the card should slide in freely as you carefully align screw holes As you feel it click into place press firmly to ensure solid seating in the slot 5...

Страница 5: ...nes for terminal block specifications Proceed to the following sections 3 0 Pin Configuration to configure the terminal blocks 4 0 Jumper Setup to configure the jumpers Acceptable Wire Size Wire Strip Length 24 16 AWG 0 24 0 28 in 6 7mm ...

Страница 6: ...urs 3 Low Battery Closed if battery is OK 4 Common UPS Fault 5 UPS Fault Closed if UPS fault occurs 6 UPS Fault Closed if no UPS failure 7 Common On Battery 8 On Battery Closed if On Battery power Utility failure 9 On Battery Closed if not On Battery power Utility OK 10 Signal Ground Use for UPS Any Mode Shutdown 11 Signal Ground Use for UPS Any Mode Shutdown 12 UPS Any Mode Shutdown Turn UPS outp...

Страница 7: ...able 2 allowing relay commons to be tied together NOTE The jumpers should be removed if there is any external volt age source that may intentionally or inadvertently be connected to the relay Removing the shunt from any two pins breaks the connection between the relay commons so they are not tied together Table 2 Jumper connections Jumper Relay P6 On Battery P5 UPS Fault P4 Low Battery P3 On Bypas...

Страница 8: ...r Road Ortigas Center Pasig City 1605 Philippines 63 2 687 6615 Fax 63 2 730 9572 The global leader in enabling Business Critical Continuity Emerson Business Critical Continuity Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co or one of its affiliated companies 2010 Emerson Electric Co AC Power Connectivity DC Power Infrastructure Man...