Important Safety Precautions
1
Liebert
®
GXT4
™
User Manual
Important Safety Precautions
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that must be followed during the installation and
maintenance of the UPS and batteries. Read this manual thoroughly before attempting
to install or operate
this UPS.
UPS Safety Notes
This UPS contains no user-serviceable parts except the internal battery pack. The Off/Bypass push button
does not electrically isolate internal parts. Under no circumstances attempt to gain internal access other
than to replace the batteries due to risk of electric shock or burn. Do not continue to use the UPS if the
front panel indications are not in accordance with these operating instructions or if the UPS performance
alters in use. Refer all faults to your local dealer, Emerson Network Power representative or Emerson
Network Power Channel Support.
This UPS has an internal battery, and the output receptacles of the UPS may carry live voltage even if the
UPS is not connected to utility input power.
Before moving or rewiring this UPS, disconnect utility input power and the battery and make sure that the
UPS is completely shut down. Otherwise, the output terminal may carry live voltage, presenting an electric
shock hazard.
To ensure human safety and normal UPS operation, the UPS must be properly grounded before use.
When the UPS is connected to an IT power distribution system, a short-circuit protection device must be
installed on the neutral line.
Install and use the Liebert GXT4 in the following environments:
• Temperature: 32°F - 104°F (0°C - 40°C), relative humidity: 0% to 95% non-condensing
• Out of direct sunlight
• Away from heat sources
• Stable surface, not subject to vibrations or shocks
• Away from dust and other particulates
• Away from corrosive substances, salts and flammable gases
Keep the air inlet and outlet of this UPS unobstructed. Poor ventilation will increase the internal
temperature of the UPS and can adversely affect the UPS and its batteries.
Keep liquid and foreign objects away from the UPS.
In case of fire, use a dry chemical fire extinguisher to put out the fire. Using a fluid fire extinguisher may
cause electric shock.
!
WARNING
Risk of electric shock. Can cause equipment damage, injury or death.
Observe all cautions and warnings in this manual. Failure to do so may result in serious injury or
death.
Refer all UPS and battery service to properly trained and qualified service personnel. Do not
attempt to service this product yourself.
Opening or removing the cover may expose you to lethal voltages within this unit even when it is
apparently not operating and the input wiring is disconnected from the electrical source.
Never work alone.
Содержание Liebert GXT4-10000RT230
Страница 1: ...Liebert GXT4 UPS 230 V 5000 VA 10 000 VA User Manual ...
Страница 2: ......
Страница 44: ...Operation and Display Panel Liebert GXT4 User Manual 36 Page intentionally left blank ...
Страница 52: ...Communication Liebert GXT4 User Manual 44 Page intentionally left blank ...
Страница 60: ...Troubleshooting Liebert GXT4 User Manual 52 Page intentionally left blank ...
Страница 67: ......