The Liebert

®

 GXT3

 UPS is ready to be powered.   

1.  Ensure the maintenance bypass breaker is in the open position and that the guard is secured in place. 
2.  Ensure that the REPO connector on the rear of the unit has a jumper between pins 1-2 of the REPO connector or 

properly wired to an Emergency Power Off circuit (normally closed). 

3.  Install any optional Intellislot communication card into the Intellislot port on the rear of the unit. 
4.  Close the input breaker in the panelboard that provides input power to the UPS 
5.  Close the input breaker on the rear of the UPS unit. Note: the UPS will now have power and the AC Input

 

indicator on the display should illuminate.  The UPS will also begin to charge the internal batteries at this point, so 
there will also be battery capacity LEDs illuminated.

 

6.  The Liebert GXT3 UPS has customizable settings that might be required depending on the application.  Please 

review the CD that ships with the UPS unit for the steps to use the configuration program and make any 
necessary changes.  Once that is complete, proceed to the next step. 

7.  Close all output breakers on the rear of the UPS 
8.  If external battery cabinets are used, close all breakers on the rear of each battery cabinet 
9. 

Press and hold for about 4 seconds, the “ON” button on the UPS display.  

Note: this will apply power to the output 

receptacles via the internal bypass and the bypass indicator will be illuminated along with an audible beep

.   

10.  Over the next several seconds the UPS will perform the self checks and startup routine then automatically 

transfer the connected equipment to the inverter power.  Once that is complete, the bypass indicator will turn off 
and the inverter indicator will illuminate.   

 
The UPS is now running in normal operation mode providing protected, filtered power to the connected equipment. 

 
 

 

 

 
 
 

 

6000VA 

DISCONTINUED

Содержание Liebert GXT3 6000VA RTL630

Страница 1: ...cture below Note the display should be located on the upper half of the unit in the Tower orientation To rotate the display with the bezels removed depress the grooved tabs on the sides and rotate it 90 degrees clockwise If the USP is to be installed in a rack enclosure follow the instructions provided with the rack mounting hardware for proper installation The UPS is cord and plug connected using...

Страница 2: ...n step 1 5 Locate the plastic bezel from the shipping box and attach the bezel to the UPS taking care to align the fastening clips on both ends before inserting them into the holes 6 If your application requires the use of external battery cabinets for longer back up time requirements connect the first battery cabinet to the UPS with the cable provided with the battery cabinet Note it does not mat...

Страница 3: ...XT3 UPS has customizable settings that might be required depending on the application Please review the CD that ships with the UPS unit for the steps to use the configuration program and make any necessary changes Once that is complete proceed to the next step 7 Close all output breakers on the rear of the UPS 8 If external battery cabinets are used close all breakers on the rear of each battery c...

Страница 4: ...onditions and battery charger failure and continuous alarm A C UPS failed battery test 2 second beep every 60 seconds A D Maintenance bypass switch on continuous A E Bypass feedback 1 second beep every 4 seconds B C REPO one quarter second beep at quarter second intervals B E Short circuit on the output C E UPS shutdown by command from communication USB or Liebert IntelliSlot port no audible alarm...

Отзывы: