Installation Instructions
21
Figure 15 Typical control wiring for units without monitoring
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
F
a
ct
or
y-
S
upp
lied
W
ir
in
g
R
24VDC W204
Overtemp Alarm N.O. W208
Overtemp Alarm N.C. W207
N.O. REPO W205
Alarm Com. W206
REPO Com. W203
N.C. REPO W202
24VDC W201
Building
Interface
Relay
Overtemp
Alarm Output
S
N.O. REPO
N.C. REPO
Remove jumper
when Normally
Closed (N.C.)
REPO is used
GRN
BLK
WHT
Low Voltage
Terminal Strip
7
A
B
9
6
3
1
4
NOTES
1. All switching devices are to be suitable for switching low current 24VDC. Minimum
recommended wire size is 18AWG stranded copper with 300V insulation.
All wiring and devices are field supplied except where noted. See installation manual for
detailed installation procedures.
2. Low voltages terminal strip may be located in unit or low voltage control junction box.
3. The total load on the 24VDC supply (both N.O. and N.C. REPO circuits) must be limited to
1A.
4. Multiple normally open (N.O.) REPO switches may be paralleled.
Multiple normally closed (N.C.) REPO switches may be connected in series. all lamps (if used)
are connected in parallel.
5. The summary alarm contacts are rated for 0 to 30VAC or VDC, 0.5A, 10W maximum.