Specifications
Liebert
®
e
XL
™
24
5.0
S
PECIFICATIONS
Table 7
Liebert
e
XL UPS specifications
Model Size
625-800kVA
Input Parameters
Input Voltage to Rectifier, VAC
480V 3-phase, 3-wire
Input Voltage to Bypass, VAC
480V 3-phase, 3-wire
Input Voltage Range, VAC
+10% to -30%
Input Frequency, Hz
60
Permissible Input Frequency Range, Hz
55 to 65
Reflected Input THDi, Nominal Voltage, Full Load, %
<5%
Power Walk-In, sec
1 to 30 (selectable) in 1 sec. Increment
Battery & DC Parameters
Battery Type
VRLA (Valve Regulated Lead Acid) or FLA
(Flooded Lead Acid)
Nominal Battery Bus, VDC
480V
Battery Float Voltage, VDC
540V
Minimum End of Discharge Voltage, VDC
384V (for VRLA / Flooded Lead Acid)
DC Ripple Voltage in Float & Const V Ch. Mode, %
<1 (RMS value) < 3,4% V
pp
Temperature Compensated Battery Charging
Optional (with temperature probe)
Output Parameters
Inverter Type
IGBT-based Sine Wave PWM Controlled
Output Power, kW
625 | 750 | 800
Output Voltage, VAC
480V 3-ph, 3-wire
Output Voltage Regulation, %
< 1% (3-phase RMS average)
Output Voltage Regulation (50% Unbalanced Load)
< 2% (3-phase RMS average)
Output Frequency, Hz
60
Output Frequency Regulation, %
± 0.1
Output THDv Linear Load at Nominal Voltage, %
<3%
Output THDv at Nominal Voltage Including a 100kVA
Non-Linear Load per EN 62040-3, %
6% (max)
Capacity to Handle High Crest Factor Load
3:1
Capacity to handle Step Load, %
0-100 or 100-0
Step Load Transient Recovery (linear loads), %
IEC 62040-3, Section 5.3.1 Figure 1
Unbalance Loads Current Capacity
100% of nominal phase current
Load Power Factor Supported (Without Derating)
0.7 Leading to 0.7 Lagging
Voltage Displacement, ° (Electrical Degree)
120° ±1° (with 50% unbalanced load)
Overload Conditions, % FL
and
Physical Parameters and Standards
Width, in (mm), With Static Bypass
123.6 (3140)
Depth, in (mm)
34.4 (874)
Height, in (mm)
77.5 (1969)
Weight, Unpackaged, lb. (kg)
approximate with Static Bypass (SMS)
5187 (2353)
Maximum Heat Dissipation, Full Load, BTU/hr (kW)
625kVA UPS: 77,348 (22.7)
750kVA UPS: 92,817 (27.2)
800kVA UPS: 101,940 (29.9)
Cooling Air, CFM
<4,800
Color
Black (ZP-7021)
Front Door Opening (for serviceability)
90°
Degree of Protection for UPS Enclosure
IP 20 (with and without front door open)
Minimum Clearance, Top, in (mm)
24 (610)
Minimum Clearance, Back, in (mm)
0