Startup
Liebert
®
CRV
™
76
10.3 Chilled Water Valve: Chilled Water 600mm (24") Models
The Liebert 600mm (24") chilled water unit comes with a two-way or three-way valve (see
The valve controls the chilled water flow and operates as follows:
• When the valve is fully open (i.e., maximum chilled water flow), the actuator slot is set to “1.”
• When the valve is closed (i.e., no chilled water flow), the actuator slot is set to “0.”
The valve running time is set to the value specified in the control manual.
Figure 49 Position of the chilled water valve actuator (for 2- or 3-way valve)—600mm (24") units
10.4 Adjust Baffles to Direct Air Properly
The Liebert CRV has been equipped with an adjustable, modular supply air baffle system. The baffles
should be adjusted prior to startup to direct air toward the racks the cooling unit is intended to
condition. Ideally, these should be the same racks the cooling unit is pulling hot air from. The baffles
can be readjusted at any time as cooling needs change.
NOTE
In the event of control system failure, the valve can be manually controlled with the ball valve
handle. It can be used to drive the actuator into any position between 0 and 1.
!
WARNING
Risk of electric shock and contact with high speed rotating fan blades. Can cause injury or
death.
Open all local and remote electric power supplies and verify with a voltmeter that power is Off
and verify that all fan blades have stopped rotating before working within the unit cabinet
and electric connection enclosures.
Ensure that the Liebert CRV is shut down and verify with a voltmeter that electric power has
been disconnected before beginning any work on the unit.
Chilled Water
Valve Actuator
Water
Supply
Piping
Water
Return
Piping