i2P-100 Transducer
Instruction Manual
Form 5777
September 2004
3
Table 1. Specifications (continued)
Electrical Housing:
NEMA 3R, CSA enclosure
Type 3R, IP66 per IEC60529
Connections
Supply and Output Pressure:
0.25 inch NPT
female connection
Vent:
0.25 inch NPT female
Electrical:
J
Standard 0.5 inch NPT
Wire Size:
18 to 22 AWG
Adjustments
(7)
Zero and Span:
Trim potentiometers (20 turn) for
zero and span adjustments are located under the
housing cap (see figure 10).
Switch:
Allows input signal split range and
user-configurable 0.2 to 2 bar (3 to 30 psig)
output.
Mounting Position
J
Actuator
J
pipestand or
J
surface
Approximate Weight (Transducer Only)
2.5 kg (5.5 lbs)
Actuator Stroking Time
See figure 2
1. These terms are defined in ISA Standard S51.1.
2. Normal m
3
/hr—Normal cubic meters per hour (0
_
C and 1.01325 bar, absolute). Scfh—Standard cubic feet per hour (60
_
F and 14.7 psia).
3. Performance values are obtained using a transducer with a 4 to 20 mA dc input signal and a 0.2 to 1.0 bar (3 to 15 psig) output signal at an ambient temperature of 24
_
C (75
_
F).
4. This product is approved for use with Natural Gas. Natural gas to contain no more than 20 ppm of hydrogen sulphide.
5. The pressure and temperature limits in this manual and any applicable standard or code limitation should not be exceeded.
6. Approvals are pending
7. For other ranges, zero and span adjustments are needed.
Table 2. Immunity Performance
Port
Phenomenon
Basic Standard
Performance Criteria
Electrostatic discharge (ESD)
IEC 61000-4-2
A
Enclosure
Radiated EM field
IEC 61000-4-3
A
Enclosure
Rated power frequency magnetic field
IEC 61000-4-8
A
Burst (fast transients)
IEC 61000-4-4
A
I/O signal/control Surge
IEC 61000-4-5
A
I/O signal/control
Conducted RF
IEC 61000-4-6
A
Specification limit =
±
1% of span
LOADING
EXHAUSTING
TIME (%)
0
10
20
30
40
50
60
70
80
90
100
0
10
20
30
40
50
60
70
80
90
100
OUTPUT
(% OF TYPE i2P-100 OUTPUT SP
AN)
A6815 / IL
Figure 2. Output-Time Relationships for Type i2P-100
Transducer
Specifications
Specifications for the Type i2P-100 transducer are
listed in table 1.
WARNING
This product is intended for a specific
current range, temperature range and
other application specifications.
Applying different current, temperature
and other service conditions could
result in malfunction of the product,
property damage or personal injury.