![Emerson FSD Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/emerson/fsd/fsd_installation-and-operation-manual_103857026.webp)
20 • FSD Installation and Operation Manual
026-1400 Rev 3 22-MAR-2011
7.5. Software Setup
1. Log on to the E2 controller
2. Navigate to the
TCP/IP
setup screen
(
Alt
+
T
).
3. Tab over to the
Peer Netwrk
tab:
4. Change
Network Type
to:
Ethernet (ETH)
and press Enter. The
Group Name
field is
now visible.
5. Once the Ethernet network type is enabled,
enter a unique site name in the
Group Name
field.
All controllers that you would like to appear in this
group must all have the same group name and must be
using the same network type.
7.6. Troubleshooting
Network troubleshooting is outside the scope of
this section (
Section 7,
E2 Ethernet Peer Communi-
cations
). Consult your IT Network Administrator for
any additional information needed.
NOTE: DHCP does not have to be enabled if
you have the IP Address, Subnet Mask, and
Primary Gateway settings. (Contact your IT
Network Administrator for all IP configuration
information.) If you do not have the IP configuration
settings, and there is a DHCP server on the network, set
DHCP Enabled to Yes and it will retrieve the informa-
tion from the server and populate those fields. E2 con-
trollers must all have the same Ethernet Subnet in order
to communicate box-to-box.
Figure 7-3
- TCPIP Setup Screen
Figure 7-4
- Peer Network Tab - Set Network Type
NOTE: If unsure of any tab settings, it is rec-
ommended that the default settings be used.
NOTE: The site name is the unique identifier
for the site that will allow the controllers within
the same group to share data.
Figure 7-5
- Peer Network Tab - Set Group Name