 TYPE FRM-2 CRYOGENIC BACK PRESSURE OR ECONOMIZER VALVE

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Before installation, these instructions must be carefully read and understood.

DESCRIPTION

The Type FRM-2 is designed to function as 
a Back Pressure or Economizer valve in 
Cryogenic Circuits. The Back Pressure function 
is to open at a preset pressure and relieve inlet 
pressure to the discharge side into a lower 
pressure. The Economizer function is to open 
at a preset pressure, above the Pressure Build 
set pressure, and continue to open as gas 
head pressure from heat leak builds during 
non-use periods of the system. The Economizer 
by-passes gas head pressure directly to the 
Final Line circuit, when system draw resumes, 
to draw down the excess pressure rapidly and 
recloses before the Pressure Build regulator 
opens. These valves are small and compact, yet 
highly efficient, making it suitable for numerous 
applications that call for a small, accurate back 
pressure regulator. Type FRM-2 incorporates a 
"floating ring" design that provides for smooth 
even pressure control.

SPECIFICATION DATA

Service:

    

Cryogenic liquids and  

 

 

gases. Well suited for  

 

 

use in the Economizer  

 

 

circuit as a heat leak  

 

 

economizer valve in   

  systems 

having 

  medium 

flows.

Sizes:

  

 

¼" (6.4 mm), ⅜" (9.5 mm)  

  and 

½" (13 mm)

Connections:

  

NPTF

Body:

  

 

Brass

Material:  

Brass

Maximum  
Temperature:

  

-320 to 150°F (-195 to 65°C)

Maximum  
Set Pressure:

  

FRM-2: 600 psig (41.4 barg)

CONSTRUCTION

Threaded ends; 2-way, side inlet-side outlet; 
2-way, side inlet-bottom outlet; 3-way, 
2 side inlets-bottom outlet; brass body; 
brass spring chamber; stainless steel seat 
disk, seat ring and pressure spring; bronze 
diaphragms; Polytetrafluoroethylene (PTFE) 
diaphragm gasket.  
Also available with stainless steel body, spring 
chamber and diaphragms. 

All parts commercially cleaned for 
cryogenic service.

Emerson.com

© 2019 Emerson. All rights reserved.

VCIOM-14770-EN 20/08

INSTALLATION INSTRUCTIONS

When installing the valve, connect the 
supply line to the inlet connection. The outlet 
connection should be connected to the bypass 
or final vaporizer line. Valves with 2 opposite 
side inlets and a bottom outlet may be installed 
as an angle valve with one inlet plugged, or 
alternatively used as an in-line valve with 
regulated pressure on both the inlet and 
process sides of the valve.

It is recommended that Type FRM-2 valve be 
installed in the horizontal position with the 
spring chamber upright. For ease of operation 
and maintenance, it is suggested that manual 
shut-off valves be installed upstream and 
downstream from the valve. Use a compatible 
sealant on the male pipe threads and do not 
overtighten the valve connections.

Other considerations in making a good 
installation are:
1.  The valve should be sized properly for the 

service conditions.

2.  Type FRM-2 valve is a diaphragm operated 

valve designed for the continuous 
operating pressure control of a system. 
All series FRM-2 valves are fitted with a 
diaphragm stop to prevent the diaphragms 
from extending beyond their limit; however, 
should a diaphragm fail, the valve will fail in 
the closed position. As a safeguard, it may 
be desirable to protect the system against 
damaging high pressures by a safety relief 
valve or some other type of safety device.